{"product_id":"honeywell-cc-taon11-51306521-175-analog-output-module","title":"Honeywell CC-TAON11 51306521-175 Analog Output IOTA Module","description":"\u003cp\u003eThe Honeywell CC-TAON11 (51306521-175) is a high-density Analog Output IOTA (Input\/Output Termination Assembly) designed specifically for the Experion PKS Series C distributed control platform. This module facilitates precise signal delivery to field-mounted actuators, control valves, and other final control elements within demanding process automation environments such as power plants, petrochemical refineries, and gas processing facilities.\u003c\/p\u003e\u003ch3\u003eFeatures\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eSupports 16 channels of analog output for high-density field device management.\u003c\/li\u003e\n\u003cli\u003eEngineered for 4-20 mA current-driven loops, ensuring signal integrity and linearity.\u003c\/li\u003e\n\u003cli\u003eIntegrated IOTA architecture streamlines field wiring and simplifies cabinet layout.\u003c\/li\u003e\n\u003cli\u003eOptimized for deterministic performance within redundant Honeywell Experion PKS control architectures.\u003c\/li\u003e\n\u003cli\u003eDesigned for rapid maintenance and module replacement to minimize system downtime.\u003c\/li\u003e\n\u003cli\u003eProvides robust channel-to-channel and field-to-system isolation.\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003eApplications\u003c\/h3\u003e\u003cp\u003eThis module is deployed in critical industrial control loops where reliable analog signal reproduction is essential. Common applications include turbine control, chemical processing, pharmaceutical manufacturing lines, and large-scale thermal power generation, where it maintains stable communication between the DCS and field instrumentation.\u003c\/p\u003e\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\u003ctable border=\"1\"\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eCC-TAON11 (51306521-175)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAnalog Output IOTA Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eExperion PKS Series C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Channels\u003c\/td\u003e\n\u003ctd\u003e16\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Signal\u003c\/td\u003e\n\u003ctd\u003e4-20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eApprox. 5 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 to 85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHumidity\u003c\/td\u003e\n\u003ctd\u003e5-95% non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eEnsure the cabinet environment meets the specified temperature and humidity ranges to prevent thermal stress.\u003c\/li\u003e\n\u003cli\u003eAlways disconnect power supply to the IOTA assembly before inserting or removing the I\/O module to prevent electrical damage.\u003c\/li\u003e\n\u003cli\u003eVerify correct wiring polarity at the termination points before commissioning to avoid loop errors.\u003c\/li\u003e\n\u003cli\u003eUse appropriate shielded cabling for analog signals to minimize electromagnetic interference (EMI) in high-noise industrial zones.\u003c\/li\u003e\n\u003cli\u003eEnsure the module is securely seated in the Series C cabinet rack to maintain proper backplane communication and grounding.\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003eFAQ\u003c\/h3\u003e\u003cp\u003e\u003cstrong\u003eIs this module compatible with redundant controller setups?\u003c\/strong\u003e\u003cbr\u003eYes, the CC-TAON11 is designed to support redundant controller architectures within the Experion PKS system, ensuring minimal signal disruption during switchovers.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eDoes this module require external power?\u003c\/strong\u003e\u003cbr\u003eThe module operates on a 24 VDC supply, typically provided through the Series C cabinet power distribution system.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":44009980362842,"sku":"CC-TAON11 51306521-175","price":172.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0710\/5957\/0778\/files\/wm_1_09b5f299-b439-44d4-bf46-99136cb215fa.jpg?v=1788499551","url":"https:\/\/www.spareoil.com\/ar\/products\/honeywell-cc-taon11-51306521-175-analog-output-module","provider":"SpareOil Automation","version":"1.0","type":"link"}