{"product_id":"ic200mdl640-ge-versamax-discrete-input-module","title":"IC200MDL640 GE VersaMax Discrete Input Module","description":"\u003cp\u003eConfigured for 24 VDC discrete signal acquisition in VersaMax PLC and I\/O station architectures, the \u003cstrong\u003eGE IC200MDL640\u003c\/strong\u003e (\u003cstrong\u003eIC200MDL640\u003c\/strong\u003e Discrete Input Module) provides direct physical\/electrical execution. The module processes field signals across 16 input points split into 2 isolated groups of 8 channels. Supporting both positive (sinking) and negative (sourcing) wiring configurations, it conditions incoming DC signals via an internal 10k Ohm impedance network and routes state data to the host CPU or Network Interface Unit (NIU) with a configurable input filter response time ranging from 0 ms to 7.0 ms.\u003c\/p\u003e\n\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIC200MDL640\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGeneral Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.11 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eStandard VersaMax Single-Slot Carrier Profile\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e25 mA @ 5 VDC (Backplane draw)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule ID\u003c\/td\u003e\n\u003ctd\u003eFFFF8008\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e16 Discrete Inputs (2 isolated groups of 8)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Operating Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC (0 to 30 VDC maximum range)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOn-State Voltage\u003c\/td\u003e\n\u003ctd\u003e15 to 30 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOff-State Voltage\u003c\/td\u003e\n\u003ctd\u003e0 to 5 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003e10k Ohms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResponse Time\u003c\/td\u003e\n\u003ctd\u003e0.5 ms basic ON\/OFF time; Configurable filter (0 ms, 1.0 ms default, 7.0 ms max)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003e250 VAC continuous group-to-group (1500 VAC for 1 min); No channel-to-channel isolation within groups\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExternal Power Requirement\u003c\/td\u003e\n\u003ctd\u003eNone\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStatus Display\u003c\/td\u003e\n\u003ctd\u003e16 point LEDs, 1 backplane \"OK\" LED\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eProfinet \/ EtherNet\/IP Deterministic Networks \u0026amp; Backplane Attributes\u003c\/h3\u003e\n\u003cp\u003eThe IC200MDL640 maintains high backplane bus communication velocity when executing cyclic I\/O scans across VersaMax carrier networks. Drawing a maximum of 25 mA from the 5 VDC logic bus, the module optimizes rack-level power allocation without requiring external field power supplies. Configurable input filter settings suppress industrial contact bounce, preserving deterministic scan timing over Profinet or EtherNet\/IP network drops. High I\/O density scaling is achieved through snap-in carrier bases, while native hardware ID flags ensure complete firmware flash compatibility and hot-swap validation during live module exchanges.\u003c\/p\u003e\n\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Does the IC200MDL640 require an auxiliary 24 VDC external power supply connection to power internal module logic?\u003c\/p\u003e\n\u003cp\u003eA: No. The internal logic and operational circuits draw all necessary power directly from the 5 VDC backplane bus at a maximum current consumption of 25 mA.\u003c\/p\u003e\n\n\u003cp\u003eQ: Can channels on the IC200MDL640 be wired in both sinking and sourcing field device configurations?\u003c\/p\u003e\n\u003cp\u003eA: Yes. The 16 input channels accommodate both positive logic (sinking current from the field device) and negative logic (sourcing current to the field device) depending on how the field device is referenced to the group common terminal.\u003c\/p\u003e\n\n\u003cp\u003eQ: Is hot-swapping supported for the IC200MDL640 module?\u003c\/p\u003e\n\u003cp\u003eA: Yes. The module supports live insertion and removal on its VersaMax carrier base; however, proper alignment and steady mechanical handling are required during insertion to prevent backplane bus communication disruption to adjacent I\/O modules.\u003c\/p\u003e\n\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003ePower Safety\u003c\/strong\u003e: Shut off main cabinet power prior to mounting, removing, or wiring carrier bases to prevent shock hazards and transient arcs.\u003c\/p\u003e\n\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eCarrier Base Snap-In\u003c\/strong\u003e: Position the IC200MDL640 module over the target VersaMax carrier slot. Press down firmly until the locking tabs snap into place, ensuring complete seating against the backplane connector.\u003c\/p\u003e\n\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eField Wiring Connections\u003c\/strong\u003e: Connect field inputs to the terminal strip on the carrier base. Connect signal wires between the input terminal and group common. When additional bussing is required, install a shorting bar on the designated carrier terminal strip.\u003c\/p\u003e\n\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eNoise Isolation \u0026amp; Shielding\u003c\/strong\u003e: Separate 24 VDC discrete signal wiring from high-voltage AC power lines and drive output cables within terminal raceways to maintain 10k Ohm input signal integrity.\u003c\/p\u003e\n\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eGrounding Verification\u003c\/strong\u003e: Ensure the carrier DIN rail or panel surface is connected to protective earth (PE) to validate the 250 VAC group-to-group isolation rating.\u003c\/p\u003e\n\n\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":43791477014618,"sku":"IC200MDL640","price":0.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0710\/5957\/0778\/files\/IC200MDL640.png?v=1785982071","url":"https:\/\/www.spareoil.com\/ar\/products\/ic200mdl640-ge-versamax-discrete-input-module","provider":"SpareOil Automation","version":"1.0","type":"link"}