100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • es

Product Description

The 10216/2/1 (Part Number: 10216/2/1) is a high-integrity fail-safe digital output (DO) module for Honeywell Fail Safe Control (FSC) systems. It features four independent 24 V DC output channels, each rated up to 2 A, designed to drive high-power safety-critical loads such as large solenoid valves, motor starters, and heavy-duty alarm devices.

Engineered for Safety Instrumented Systems (SIS), the module continuously monitors its fail-safe functionality, ensuring that outputs de-energize automatically during emergencies. Integrated suppression diodes protect against inductive load effects, and the module is TUV-certified for SIL 3 applications, making it ideal for use in oil, gas, and petrochemical industries.


Technical Specifications

Parameter Specification
Model Number 10216/2/1 (10216-2-1)
Module Type Reference 11502
Output Channels 4 Independent Fail-Safe Channels
Output Voltage 24 V DC
Maximum Current 2.0 A per channel
Maximum Load per Channel 48 W
Safety Testing Automatic de-energization, crosstalk detection, component integrity check
Inductive Load Protection Built-in suppression diodes on all outputs
Internal Power Consumption 5 V DC at 35 mA
External Field Power 24 V DC
Space Requirements 4 HP width (TE), 3U height (HE)
Key Coding Holes A15, C15 / Pins A15, C15
Certifications CE, TUV SIL-3, UL
Physical Dimensions 3 cm × 20 cm × 15 cm
Unit Weight 0.20 kg

Application Scenarios

  • Driving high-power ESD solenoid valves in refinery tank farms

  • Activating fire suppression system release solenoids

  • Controlling interposing relays for motor isolation in safety loops

  • Managing power-intensive alarms and signaling devices in hazardous areas


Frequently Asked Questions

How does the 10216/2/1 differ from the 10201/2/1 module?
The 10216/2/1 supports higher current (2 A per channel) over 4 channels, whereas the 10201/2/1 provides lower current (550 mA) over 8 channels.

Can this module be used in SIL-3 safety loops?
Yes. When integrated into a properly configured Honeywell FSC system, the 10216/2/1 is TUV-certified for SIL-3 safety applications.

What's clients say about us