100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • es

Product Description

The DECS-200-1L by Basler Electric is a digital excitation control system engineered for precise synchronous generator management. This high-speed voltage regulator provides stable DC field current for a wide range of generator sizes and applications. Its versatile design supports both single-phase and three-phase AC inputs with a broad frequency tolerance, making it suitable for standard, industrial, and specialized high-frequency power systems.

The DECS-200-1L delivers 15 A continuous DC output to the generator field and integrates advanced protection logic, including overexcitation (OEL) and underexcitation (UEL) limiting, safeguarding equipment during transient load conditions. Its digital architecture allows for fine-tuned PID control, ensuring exceptional system stability and reliable generator operation in critical power environments.


Technical Specifications

Specification Details
Model DECS-200-1L
Control Type Digital Excitation Control System (DECS)
AC Input Voltage 56–277 VAC, 1-Phase or 3-Phase
Input Frequency 50–400 Hz
Continuous DC Output 15 A
Selectable DC Output Voltage 32 VDC, 63 VDC, 125 VDC
Internal Power Supply 24/48 VDC (30 W)
Input Current Rating 11 A continuous, 20 A forcing
Regulation Accuracy ±0.25% of voltage setpoint
Enclosure Weight 5.9 kg 
Protection Features Overexcitation Limiter (OEL), Underexcitation Limiter (UEL)

Application Scenarios

The DECS-200-1L is ideal for:

  • Hydroelectric plants

  • Industrial cogeneration facilities

  • Marine propulsion systems

  • Aviation and military ground power units requiring 400 Hz compatibility

Its high-frequency tolerance and robust protection features ensure safe, stable operation across diverse generator configurations and transient load conditions.


Frequently Asked Questions

Q: How does the DECS-200-1L handle varying power sources?
A: The unit features an auto-sensing input stage that accommodates both single-phase and three-phase AC inputs. The DC output voltage (32, 63, or 125 VDC) can be selected via internal jumpers or software configuration to match the generator’s field requirements.

Q: Why is 400 Hz input support important?
A: Standard grids operate at 50/60 Hz, but the DECS-200-1L can maintain stable operation in high-frequency environments, making it compatible with permanent magnet generators (PMG) and high-speed turbine applications.