{"product_id":"digital-input-module-specs-yokogawa-adv151-p53-d5a00","title":"Digital Input Module Specs Yokogawa ADV151-P53\/D5A00","description":"\u003ch1\u003eYokogawa ADV151-P53\/D5A00 Digital Input Module\u003c\/h1\u003e\n\u003cp\u003eConfigured for high-speed discrete signal acquisition in CENTUM VP and CS 3000 platforms, the\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eYokogawa ADV151-P53\/D5A00\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e(\u003cstrong\u003eADV151-P53\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eDigital Input Module) provides direct physical electrical sensing for field-side process interlocks and status monitoring.\u003c\/p\u003e\n\u003ch3\u003eSuffix Breakdown \u0026amp; Model Matrix\u003c\/h3\u003e\n\u003cp\u003eThe\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eADV151\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003ebase model defines the 32-channel digital input configuration (utilized here as 16 isolated channels). The suffix codes specify the following hardware parameters:\u003c\/p\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003e-P\u003c\/strong\u003e: Standard hardware type.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003e5\u003c\/strong\u003e: Version without integral status display, excluding explosion protection certification.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003e3\u003c\/strong\u003e: Equipped with ISA Standard G3 corrosion resistance and an extended operating temperature range (-20 deg C to +70 deg C).\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eOption \/D5A00\u003c\/strong\u003e: Includes the ATD5A-00 KS cable interface adapter for simplified signal distribution.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr class=\"firstRow\"\u003e\n\u003ctd\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eModel\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eADV151-P53\/D5A00\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eBrand\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eYokogawa\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eOrigin\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eJapan\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eWeight\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e0.2 kg\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eDimensions\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e107.5 x 130 x 32.8 mm\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eOperating Temp\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e-20 deg C to +70 deg C\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003ePower Consumption\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e3–4 W\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eInput Channels\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e16 (isolated)\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eInput Voltage\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e24 VDC (20.4–26.4 VDC)\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eResponse Time\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e\u0026lt;= 3 ms\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003ch3\u003eDCS Process Control Connectivity\u003c\/h3\u003e\n\u003cp\u003eThe\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eADV151-P53\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eutilizes channel-to-channel isolation and optical barrier separation from the system bus to maintain signal integrity in industrial environments. This configuration effectively suppresses common-mode transients and prevents cross-talk between high-density input loops. The module supports 4-20 mA HART loop protocol translation when utilized with compatible analog subsystems, providing unified diagnostic data handling across the CENTUM VP architecture. Each channel employs current-sink detection to identify field circuit states, ensuring deterministic performance for time-critical interlock signals.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions (FAQ)\u003c\/h3\u003e\n\u003cp\u003eQ: Does the ADV151-P53 support on-line module replacement?\u003c\/p\u003e\n\u003cp\u003eA: Yes. The module is engineered with hot-swap capability, allowing for removal and insertion into the powered rack assembly without requiring a system shutdown or impacting the operational status of adjacent I\/O modules.\u003c\/p\u003e\n\u003cp\u003eQ: What are the primary advantages of the \/D5A00 adapter inclusion?\u003c\/p\u003e\n\u003cp\u003eA: The \/D5A00 (ATD5A-00) interface adapter facilitates the use of standard KS cables, significantly reducing field wiring labor and potential termination errors during the installation of 32-channel digital input arrays.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eMounting Protocol:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eSecure the module within the designated rack slot. Verify the locking mechanism is fully engaged to ensure robust electrical contact with the backplane bus.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eEnvironmental Shielding:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eThe module is rated for IP20. Ensure it is installed within a NEMA-rated enclosure to prevent exposure to corrosive particulates or condensation.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eWiring Practices:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eUtilize shielded twisted-pair cabling for all discrete inputs. Terminate shields at the cabinet-integrated ground bus to minimize EMI\/RFI noise injection. Ensure field wiring does not exceed the 26.4 VDC maximum voltage threshold.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eElectrical Verification:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003ePrior to system activation, measure the input voltage at the terminal block to ensure it resides within the 20.4 VDC to 26.4 VDC operating range.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Yokogawa","offers":[{"title":"Default Title","offer_id":43612073427034,"sku":"ADV151-P53","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0710\/5957\/0778\/files\/173._63ae5bce-7f95-4f41-8f5a-f0bcc772fc41.jpg?v=1783405027","url":"https:\/\/www.spareoil.com\/es\/products\/digital-input-module-specs-yokogawa-adv151-p53-d5a00","provider":"SpareOil Automation","version":"1.0","type":"link"}