{"product_id":"digital-input-module-technical-specs-yokogawa-adv169-p01","title":"Digital Input Module Technical Specs Yokogawa ADV169-P01","description":"\u003ch2\u003eYokogawa ADV169-P01 Digital Input Module\u003c\/h2\u003e\n\u003cp\u003eConfigured for discrete signal acquisition in CENTUM VP and CS 3000 platforms, the\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eYokogawa ADV169-P01\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e(\u003cstrong\u003eADV169-P01\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eDigital Input Module) provides direct physical electrical sensing for field-side process monitoring.\u003c\/p\u003e\n\u003ch3\u003eSuffix Breakdown \u0026amp; Model Matrix\u003c\/h3\u003e\n\u003cp\u003eThe\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eADV169-P01\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003edesignation defines the base 32-channel digital input configuration. The module is engineered for high-density signal processing within standard Yokogawa rack assemblies. The P01 suffix identifies the primary hardware revision compatible with standard 24 VDC discrete logic circuits, facilitating direct interface with field limit switches, pressure sensors, and process interlock contacts.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr class=\"firstRow\"\u003e\n\u003ctd\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eModel\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eADV169-P01\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eBrand\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eYokogawa\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eOrigin\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eJapan\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eWeight\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e0.2 kg\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eDimensions\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e107.5 x 130 x 32.8 mm\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eOperating Temp\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e0 deg C to +60 deg C\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003ePower Consumption\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e4 W\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eInput Channels\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e32\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eInput Voltage\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e24 VDC (20.4–26.4 VDC)\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eResponse Time\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e\u0026lt;= 3 ms\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003ch3\u003eDCS Process Control Connectivity\u003c\/h3\u003e\n\u003cp\u003eThe\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eADV169-P01\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003emodule utilizes channel-to-channel isolation and robust optical barrier separation from the system bus to maintain signal integrity in industrial environments. This design configuration supports 4-20 mA HART loop protocol integration when utilized in conjunction with associated analog input subsystems, ensuring unified data handling across the CENTUM VP architecture. The module provides continuous status verification, with each channel employing current-sink detection to identify field circuit states, effectively suppressing common-mode transients and minimizing cross-talk between high-density input loops.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions (FAQ)\u003c\/h3\u003e\n\u003cp\u003eQ: Does the ADV169-P01 support on-line replacement?\u003c\/p\u003e\n\u003cp\u003eA: Yes. The module is designed with hot-swap capability, permitting removal and insertion into the powered rack assembly without requiring a system shutdown or affecting the operational state of adjacent I\/O modules.\u003c\/p\u003e\n\u003cp\u003eQ: How does the module handle signal transient protection?\u003c\/p\u003e\n\u003cp\u003eA: The input circuitry incorporates optical isolation providing a 2 kV AC dielectric withstand rating for 1 minute between the field input and the system bus, shielding internal logic from high-voltage field-side surges.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eMounting Protocol:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eSecure the module within the designated rack slot, ensuring the backplane connector aligns correctly. Verify the module locking mechanism is fully engaged to maintain electrical contact and structural stability.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eEnvironmental Shielding:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eThe module is rated for IP20 environments. Ensure it resides within a NEMA or equivalent rated cabinet to prevent exposure to corrosive particulates, high humidity, or direct moisture.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eWiring Practices:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eUtilize shielded twisted-pair cabling for all discrete inputs to minimize EMI interference. Terminate shields at the cabinet-integrated ground bus. Ensure field wiring does not exceed the voltage capacity of 26.4 VDC to prevent input stage degradation.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eElectrical Checks:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eBefore activating the system, measure the input voltage at the terminal block to ensure it falls within the 20.4 VDC to 26.4 VDC nominal operating range.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Yokogawa","offers":[{"title":"Default Title","offer_id":43611664023642,"sku":"ADV169-P01","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0710\/5957\/0778\/files\/164.1_1e1447bb-eddf-4255-8aa0-817b488db776.jpg?v=1783396826","url":"https:\/\/www.spareoil.com\/es\/products\/digital-input-module-technical-specs-yokogawa-adv169-p01","provider":"SpareOil Automation","version":"1.0","type":"link"}