{"product_id":"ge-fanuc-ic200alg264-versamax-analog-input-module","title":"GE Fanuc IC200ALG264 VersaMax Analog Input Module","description":"\u003cp\u003eThe \u003cstrong\u003eGE Fanuc IC200ALG264\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eIC200ALG264\u003c\/strong\u003e 15-Point Analog Current Input Module, operates as a dedicated hardware component for single-ended current signal acquisition within VersaMax I\/O platforms. The module processes 15 analog current channels configured in a single group, converting 0-20 mA or 4-20 mA signals into 15-bit digital values for backplane transmission to the main CPU.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIC200ALG264\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE Fanuc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.50 lbs (0.23 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eSingle slot VersaMax footprint\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 deg C to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e100 mA maximum at 5 VDC from PLC backplane\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e15 single-ended inputs (1 group)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAnalog Resolution\u003c\/td\u003e\n\u003ctd\u003e15 bits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Ranges\u003c\/td\u003e\n\u003ctd\u003e0-20 mA, 4-20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDigital Resolution\u003c\/td\u003e\n\u003ctd\u003e0.5 uA (4-20 mA), 0.625 uA (0-20 mA)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003e100 Ohms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFilter Response\u003c\/td\u003e\n\u003ctd\u003e24 Hz +\/-20% (3dB corner frequency)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUpdate Rate\u003c\/td\u003e\n\u003ctd\u003e7.5 ms maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003e250 VAC continuous, 1500 VAC for 1 minute\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiagnostic Features\u003c\/td\u003e\n\u003ctd\u003eLoss of internal power, open wire detection (4-20 mA mode)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eBackplane Bus Communication Velocity \u0026amp; Firmware Flash Compatibility\u003c\/h3\u003e\n\u003cp\u003eThe module executes high-speed serial data exchanges over the VersaMax backplane bus, completing full 15-channel data updates within a maximum cycle time of 7.5 ms. Field signals pass through dedicated Analog-to-Digital Converter (ADC) circuits with hardware 24 Hz low-pass filtering, suppressing ambient electrical transients before writing 15-bit digital outputs directly to CPU memory tables. Range execution operates via terminal hardware jumpers; removing the jumper selects default 4-20 mA processing, while installing the jumper configures 0-20 mA operation without requiring firmware re-flashing.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How is the input range switched between 4-20 mA and 0-20 mA?\u003c\/p\u003e\n\u003cp\u003eA: Signal range selection is determined physically by the terminal jumper configuration. Leaving the terminal jumper uninstalled configures 4-20 mA operation, whereas installing the jumper sets the module to 0-20 mA operation.\u003c\/p\u003e\n\u003cp\u003eQ: Does open wire diagnostic detection function in both signal range modes?\u003c\/p\u003e\n\u003cp\u003eA: No, open wire detection is active only when operating in the 4-20 mA mode. Loss of internal power diagnostics remains active in both operating modes.\u003c\/p\u003e\n\u003cp\u003eQ: Is channel-to-channel isolation provided on the 15 input channels?\u003c\/p\u003e\n\u003cp\u003eA: No, all 15 single-ended channels belong to a single common group and share the same return potential, providing group isolation of 250 VAC continuous to the backplane, but no isolation between individual channels.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eMount the module chassis firmly onto a standard DIN rail or panel plate within the VersaMax rack alignment.\u003c\/li\u003e\n\u003cli\u003eEnsure system power is disconnected before seating the module into its corresponding terminal carrier interface.\u003c\/li\u003e\n\u003cli\u003eWire field transmitters to the 15 single-ended channel terminals, ensuring sensor power supplies match loop compliance requirements.\u003c\/li\u003e\n\u003cli\u003eSet hardware jumpers on the terminal block base according to the targeted input signal format (uninstalled for 4-20 mA, installed for 0-20 mA).\u003c\/li\u003e\n\u003cli\u003eTerminate input cable shields at a dedicated system grounding bar to maintain noise immunity and backplane signal integrity.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":43796895727706,"sku":"IC200ALG264","price":0.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0710\/5957\/0778\/files\/IC200ALG264.jpg?v=1786090897","url":"https:\/\/www.spareoil.com\/es\/products\/ge-fanuc-ic200alg264-versamax-analog-input-module","provider":"SpareOil Automation","version":"1.0","type":"link"}