{"product_id":"bently-nevada-135785-01-3500-93-system-display-module","title":"Bently Nevada 135785-01 3500\/93 System Display Module","description":"\u003ch2\u003eBently Nevada 3500\/93 135785-01 Display Interface Module\u003c\/h2\u003e\n\u003cp\u003eConfigured for local visualization and real-time operator interface execution in Bently Nevada 3500 Machinery Protection System platforms, the \u003cstrong\u003eBently Nevada 135785-01\u003c\/strong\u003e (\u003cstrong\u003e3500\/93\u003c\/strong\u003e Display Interface Module) provides direct physical\/electrical execution. This module connects across the internal backplane bus to extract real-time telemetry from channel monitors, relay states, and Keyphasor tachometer readings. Operating at 12 VDC input voltage, it formats digital asset condition data into a 640 x 480 pixel graphical LCD layout, providing local visibility for channel values, alarm logs, and system event lists without affecting primary protection machinery logic.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eModel\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3500\/93 (135785-01)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eBently Nevada\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOrigin\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eWeight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.2 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e150 mm x 120 mm x 30 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOperating Temp\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e-40 to +85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower Consumption\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDriven by 12 VDC input voltage\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDisplay Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eBacklit graphical LCD\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eResolution\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e640 x 480 pixels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInternal Refresh Rate\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e200 Hz internal acquisition\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCommunication Interface\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eEthernet\/IP (via Display Interface Module)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMounting Options\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eFace mount (Slot 15), Panel mount, or Independent remote mount\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAPI Compliance\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAPI 670 machinery protection standards compliant\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eStorage Temp\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e-40 to +105 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eRotor Dynamics and Gap Voltage Validation Parameters\u003c\/h3\u003e\n\u003cp\u003eThe 3500\/93 135785-01 display module visualizes high-speed dynamic telemetry generated by proximity transducing systems without interfering with primary trip relays. As proximity probes convert shaft displacement into analog signals, eddy-current probe scaling metrics (such as standard 200 mV\/mil or 7.87 V\/mm) pass across the backplane to render dynamic channel trends directly on the LCD panel. Field technicians monitor real-time gap voltage validation (-10 VDC nominal targets) to verify physical probe position relative to baseline centerline offsets. By displaying simultaneous Keyphasor rotational speed and vibration channels alongside internal cross-talk suppression status across adjacent slots, the display allows immediate field analysis of shaft centerline position, unbalance, and rotor dynamics stability.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Is the 3500\/93 135785-01 display module cross-compatible with the 3500\/94 VGA display architecture?\u003c\/p\u003e\n\u003cp\u003eA: No, the 135785-01 operates strictly within the dedicated 3500\/93 LCD framework and cannot drive standard external VGA monitors designed for 3500\/94 display interfaces.\u003c\/p\u003e\n\u003cp\u003eQ: Which rack position must house the Display Interface Module during face-mount installation?\u003c\/p\u003e\n\u003cp\u003eA: For face-mounted chassis layouts, the accompanying display interface hardware must occupy Slot 15 (the right-most slot of the 3500 chassis) to connect directly with the LCD unit.\u003c\/p\u003e\n\u003cp\u003eQ: What operational response occurs if communication between the display module and the backplane drops?\u003c\/p\u003e\n\u003cp\u003eA: A loss of display communication triggers an internal diagnostic fault indication on the display interface while primary protection monitoring cards and machinery safety trip relays continue independent execution.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eWhen installing the Bently Nevada 3500\/93 135785-01 display unit in an industrial monitoring chassis, follow these engineering steps:\u003c\/p\u003e\n\u003col\u003e\n\u003cli\u003eDe-energize cabinet power or follow site hot-swap safety protocols before seating the display interface card into Slot 15 of the 3500 rack.\u003c\/li\u003e\n\u003cli\u003eAlign the module chassis edges with the guide rails and slide the assembly backward until the backplane connectors seat securely.\u003c\/li\u003e\n\u003cli\u003eTighten the upper and lower panel captive screws to 0.6 N m torque to ensure continuous chassis grounding and immunity against electrostatic discharge.\u003c\/li\u003e\n\u003cli\u003eRoute the dedicated display interconnect cabling away from high-voltage AC power lines and variable frequency drive outputs to avoid electrical noise interference.\u003c\/li\u003e\n\u003cli\u003eBond the mounting panel or display housing shield to the cabinet single-point ground system in accordance with API 670 installation standards.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"Bently Nevada","offers":[{"title":"Default Title","offer_id":43092120731738,"sku":"3500\/93 135785-01","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0710\/5957\/0778\/files\/287.jpg?v=1774248759","url":"https:\/\/www.spareoil.com\/products\/bently-nevada-135785-01-3500-93-system-display-module","provider":"SpareOil Automation","version":"1.0","type":"link"}