{"product_id":"field-control-analog-current-input-module-ge-ic670alg230","title":"Field Control Analog Current Input Module | GE IC670ALG230","description":"\u003ch2\u003eGE Fanuc IC670ALG230 Field Control I\/O\u003c\/h2\u003e\n\u003cp\u003eConfigured for high-density single-ended analog data capture in distributed Genius Bus networks, the \u003cstrong\u003eGE Fanuc IC670ALG230\u003c\/strong\u003e (\u003cstrong\u003eIC670ALG230\u003c\/strong\u003e Analog Current Input Module) provides direct physical\/electrical execution. This hardware component converts 0-20 mA or 4-20 mA loop currents into 12-bit digital data across eight single-ended channels. The module executes signal digitized conversion within 60 microseconds per channel and forwards these data bits directly to the head-end Bus Interface Unit (BIU). A 1500 VAC electrical barrier isolates the field-side loops from the internal processing architecture to block transient surges.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIC670ALG230\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE Fanuc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.26 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eStandard Field Control footprint\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e51 mA maximum from BIU backplane\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e8 (Single-ended)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Signal Range\u003c\/td\u003e\n\u003ctd\u003e0.0 mA to 25.0 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDigital Resolution\u003c\/td\u003e\n\u003ctd\u003e12-bit (5.0 uA per LSB)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConversion Time\u003c\/td\u003e\n\u003ctd\u003e60 microseconds per channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003e250 ohms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExternal Power Supply\u003c\/td\u003e\n\u003ctd\u003e24 VDC (18-30 VDC range)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003e1500 VAC (1 minute), 250 VAC (Continuous)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNon-linearity\u003c\/td\u003e\n\u003ctd\u003eplus or minus 0.025% of full scale\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAccuracy\u003c\/td\u003e\n\u003ctd\u003eplus or minus 0.05% of full scale at 25 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eIndustrial Control Backplane and Network Integration\u003c\/h3\u003e\n\u003cp\u003eThe module implements software-selectable 50 Hz or 60 Hz digital notch filters to reject ambient industrial electrical noise from corrupting data registers. Backplane bus communication velocity handles the continuous stream of 12-bit processed values, matching the module-level conversion latency. Users scale I\/O density by slot configuration on the local Field Control basebook. Firmware flash compatibility rules require that the head-end Bus Interface Unit recognizes the device hardware ID to maintain appropriate network synchronization across the deterministic distributed Genius Bus topology.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How does the module react if an external 24 VDC loop power supply drops below 18 VDC?\u003c\/p\u003e\n\u003cp\u003eA: The hardware detects the undervoltage fault, ceases valid conversion cycles, and drives corresponding diagnostic failure bits to the BIU over the backplane bus.\u003c\/p\u003e\n\u003cp\u003eQ: Can the internal analog-to-digital matrix withstand continuous high-voltage spikes?\u003c\/p\u003e\n\u003cp\u003eA: The module maintains continuous galvanic isolation up to 250 VAC. Transient exposures up to 1500 VAC are withstood for a maximum duration of 1 minute without destruction of internal components.\u003c\/p\u003e\n\u003cp\u003eQ: Does the 250 ohm input impedance require an external precision shunt resistor?\u003c\/p\u003e\n\u003cp\u003eA: No, the 250 ohm precision termination resistors are completely integrated into the physical circuit layout of each individual input channel.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eSecure the module onto the Field Control baseplate terminal unit, verifying full mechanical engagement of the backplane connectors.\u003c\/li\u003e\n\u003cli\u003eRoute all 4-20 mA analog signal wires through dedicated, shielded twisted-pair cables to mitigate electromagnetic coupling.\u003c\/li\u003e\n\u003cli\u003eGround the overall cable shield at one single end on the chassis ground rail to prevent the generation of ground loop currents.\u003c\/li\u003e\n\u003cli\u003eEnsure external 24 VDC loop power connections conform to the specified 18-30 VDC hardware operational window.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":42870840590426,"sku":"IC670ALG230","price":0.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0710\/5957\/0778\/files\/201.1.jpg?v=1772242673","url":"https:\/\/www.spareoil.com\/products\/field-control-analog-current-input-module-ge-ic670alg230","provider":"SpareOil Automation","version":"1.0","type":"link"}