{"product_id":"foxboro-p0917yz-fcp270-ecostruxure-dcs-cpu-module","title":"Foxboro P0917YZ FCP270 EcoStruxure DCS CPU Module","description":"\u003ch2\u003eFoxboro P0917YZ FCP270 Field Control Processor Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eFoxboro P0917YZ\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eFCP270\u003c\/strong\u003e Field Control Processor Module, operates as a dedicated hardware component for regulatory, logic, timing, and sequential control execution within EcoStruxure Foxboro DCS platforms.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFCP270\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eFoxboro by Schneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.6 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e114 mm x 51.5 mm x 147 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 deg C to +60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e8.5 W maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePart Number\u003c\/td\u003e\n\u003ctd\u003eP0917YZ\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMemory Capacity\u003c\/td\u003e\n\u003ctd\u003e16 MB SDRAM \/ 32 MB Flash\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommunication Speed\u003c\/td\u003e\n\u003ctd\u003e100 Mbps (Fiber Optic Ethernet)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum FBM Support\u003c\/td\u003e\n\u003ctd\u003eUp to 32 Fieldbus Modules\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eProcess Control \u0026amp; DCS Network Performance\u003c\/h3\u003e\n\u003cp\u003eThe processor manages deterministic data transmission to connected fieldbus modules, maintaining isolated 4-20 mA HART loop protocol parameters across sub-networks. Internal memory buffers preserve FOUNDATION Fieldbus \/ Profibus PA connectivity throughput during peak scan cycles. Configured with channel-to-channel isolation circuits and integrated cold junction compensation (CJC) algorithms for remote temperature inputs, the unit executes fault-tolerant failover without losing loop scan timing.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Does the P0917YZ processor support hot-swappable installation in a redundant baseplate?\u003c\/p\u003e\n\u003cp\u003eA: Yes, in a fault-tolerant paired baseplate configuration, a technician can insert or remove a secondary P0917YZ module while the primary processor continues control execution without loop disruption.\u003c\/p\u003e\n\u003cp\u003eQ: How does the module maintain control configuration during a complete power failure?\u003c\/p\u003e\n\u003cp\u003eA: The onboard 32 MB flash memory retains the non-volatile system image and database, allowing automatic re-initialization upon restoration of 24 VDC power.\u003c\/p\u003e\n\u003cp\u003eQ: What mounting restrictions apply when installing the FCP270 hardware?\u003c\/p\u003e\n\u003cp\u003eA: The FCP270 requires dedicated FCP270-compatible baseplates (such as P0926CP) and cannot be inserted into legacy FCP240 or FCP100 baseplate slots without specific hardware baseplate adapters.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eMount the P0917YZ module firmly onto its dedicated baseplate slot until the locking levers engage fully to establish secure backplane contact. Connect dual 24 VDC power feeds from independent power supplies to ensure continuous redundant operation. Ensure fiber optic Ethernet cables maintain minimum specified bend radii and that connectors are free of dust before mating to preserve optical signal integrity. Ground the baseplate chassis directly to the primary cabinet earth ground bus using a heavy gauge grounding strap to eliminate ground loop interference.\u003c\/p\u003e","brand":"Foxboro","offers":[{"title":"Default Title","offer_id":43094979575898,"sku":"FCP270 P0917YZ","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0710\/5957\/0778\/files\/297_dde17ee8-19f8-4563-82ce-706a9b06011c.jpg?v=1774253689","url":"https:\/\/www.spareoil.com\/products\/foxboro-p0917yz-fcp270-ecostruxure-dcs-cpu-module","provider":"SpareOil Automation","version":"1.0","type":"link"}