{"product_id":"woodward-5466-425d-micronet-datasheet-technical-manual","title":"Woodward 5466-425D MicroNet Datasheet \u0026 Technical Manual","description":"\u003ch2\u003eWoodward 5466-425D MicroNet Analog I\/O Module\u003c\/h2\u003e\n\u003cp\u003eConfigured for high density analog signal conversion in MicroNet Control systems, the \u003cstrong\u003eWoodward 5466-425D\u003c\/strong\u003e (\u003cstrong\u003e5466-425\u003c\/strong\u003e Analog I\/O Module) provides direct physical\/electrical execution.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e5466-425D\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eWoodward\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.9 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e2.4 cm x 24.6 cm x 26.1 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to +85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e24 VDC (+\/-10%)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Range\u003c\/td\u003e\n\u003ctd\u003e0-25 mA (+\/-0.1% FS accuracy)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Range\u003c\/td\u003e\n\u003ctd\u003e0-20 mA (+\/-0.2% FS accuracy)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUpdate Time\u003c\/td\u003e\n\u003ctd\u003e5 ms per channel (synchronous sampling)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Isolation\u003c\/td\u003e\n\u003ctd\u003e500 VDC (channel-to-channel and to ground)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEnclosure \/ Housing\u003c\/td\u003e\n\u003ctd\u003eFlame-retardant metal (UL94 V-0)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eActuator Loop Feedback Response\u003c\/h3\u003e\n\u003cp\u003eThe hardware employs synchronous sampling routines delivering a 5 ms per channel update interval to optimize the actuator loop feedback response. This high-density architecture translates current signals ranging from 0 to 25 mA into digital data for the core controller while driving external actuators via 0 to 20 mA analog outputs. By maintaining 500 VDC channel-to-channel and channel-to-ground galvanic isolation, the module prevents ground loop currents from degrading turbine governor calculation tracking or introducing jitter into actuator positioning loops.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Does the module support hot-swap insertion and removal during live system operation?\u003c\/p\u003e\n\u003cp\u003eA: Yes, the hardware design supports hot-swappable replacement procedures, allowing maintenance without requiring a complete shutdown of the MicroNet control chassis.\u003c\/p\u003e\n\u003cp\u003eQ: What is the maximum voltage threshold for the electrical isolation circuits on this unit?\u003c\/p\u003e\n\u003cp\u003eA: The module features continuous galvanic isolation rated at 500 VDC applied between independent channels and from channel blocks to the backplane ground.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eMounting Orientation and Seating:\u003c\/strong\u003e Secure the module within its assigned chassis slot or onto a 35 mm DIN rail. Tighten all hardware retention fasteners to ensure robust electrical continuity with the chassis ground plane.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eShielding and Termination:\u003c\/strong\u003e Use twisted, shielded pair cabling for all 0-25 mA inputs and 0-20 mA outputs. Terminate the shield drains at the designated single-point chassis ground bar to mitigate electromagnetic interference.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eEnvironmental Considerations:\u003c\/strong\u003e Verify that the installation enclosure maintains ambient operating temperatures between -40 deg C and +85 deg C under non-condensing relative humidity levels up to 95%.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Woodward","offers":[{"title":"Default Title","offer_id":43475332071514,"sku":"5466-425D","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0710\/5957\/0778\/files\/178_ede92ca7-bc7b-46d3-b064-3ecc15f712b2.jpg?v=1781062834","url":"https:\/\/www.spareoil.com\/products\/woodward-5466-425d-micronet-datasheet-technical-manual","provider":"SpareOil Automation","version":"1.0","type":"link"}