{"product_id":"yokogawa-aat141-s00-centum-analog-input-module","title":"Yokogawa AAT141-S00 CENTUM Analog Input Module","description":"\u003ch2\u003eYokogawa AAT141-S00 CENTUM Analog Input Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eYokogawa AAT141-S00\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eAAT141\u003c\/strong\u003e Analog Input Module, operates as a dedicated hardware component for converting analog current signals into digital variables within CENTUM VP and CS 3000 Field Control Stations. The module manages the electrical interface for 16 distinct measurement paths, translating raw current transitions into 16-bit registers across the inner system bus. By executing continuous galvanic separation between field terminals and the central logic engine, the card isolates tracking signals across the network topology.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eAAT141-S00\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eYokogawa\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eJapan\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.3 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e33 mm x 107 mm x 130 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-10 to +60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eNot Specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAnalog Input Modules\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e16 channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Type\u003c\/td\u003e\n\u003ctd\u003e4-20 mA DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResolution\u003c\/td\u003e\n\u003ctd\u003e16-bit A\/D conversion\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAccuracy\u003c\/td\u003e\n\u003ctd\u003e+\/-0.1% of full scale\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003e250 Ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003eGalvanic isolation per channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Supply\u003c\/td\u003e\n\u003ctd\u003e24 VDC nominal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eProcess Control and Deterministic Loop Characteristics\u003c\/h3\u003e\n\u003cp\u003eThe instrument layout implements individual instrumentation interfaces designed to decode the standard 4-20 mA HART loop protocol without inducing voltage drop fluctuations across the input network. Channel-to-channel isolation components maintain physical partition boundaries that obstruct common-mode noise propagation, preventing transient faults from affecting neighboring data paths. Active diagnostic logic interrogates each internal loop configuration to trace circuit errors, running real-time tracking loops that report open-circuit conditions and loop short-circuit faults straight to the central processing matrix.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How does the internal 250 Ohm input impedance circuit alter module operation if an external short-circuit occurs?\u003c\/p\u003e\n\u003cp\u003eA: The internal current-limiting components tolerate temporary line shorts by isolating the impacted channel. The dedicated onboard diagnostics immediately trigger a loop fault register, notifying the controller backplane while protecting the remaining 15 analog input circuits from thermal breakdown.\u003c\/p\u003e\n\u003cp\u003eQ: Does this specific hardware version permit online hot-swap operations within an active node chassis?\u003c\/p\u003e\n\u003cp\u003eA: Live replacement relies on the structural configuration of the host node slot. Operators must confirm that the system software parameter blocks and slot allocation configurations support hot-swap routines before extracting the module from the active backplane connector.\u003c\/p\u003e\n\u003cp\u003eQ: What action occurs within the 16-bit A\/D converter when a field sensor signal falls outside the standard 4-20 mA envelope?\u003c\/p\u003e\n\u003cp\u003eA: The converter tracks down to the hardware under-range and over-range saturation thresholds. If the signal deviates past these engineering parameter limits, the module attaches an invalid data flag to the variable sent across the backplane bus.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eChassis Earth Grounding:\u003c\/strong\u003e Secure the hardware firmly into its rack slot, verifying that the grounding contacts press tightly against the bare metal frame of the sub-rack to ensure an uninhibited path to earth.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDrain Wire Shield Matrix:\u003c\/strong\u003e Connect all instrument cable shields to a common copper grounding bar positioned inside the lower section of the enclosure. Avoid routing shield wires directly into the front signal connector plugs.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSeparation of Signal Conductors:\u003c\/strong\u003e Route all incoming 4-20 mA signal wires inside segregated plastic wiring conduits, keeping a minimum clearance of 200 mm away from high-power AC supply distribution lines or drive cables.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConnector Tension Testing:\u003c\/strong\u003e Check all terminal retention screws using standard torque limits to ensure the multi-pin connector remains securely attached, eliminating vibration-induced resistance shifts on the current loops.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Yokogawa","offers":[{"title":"Default Title","offer_id":43660805079130,"sku":"AAT141-S00","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0710\/5957\/0778\/files\/162.1_ac299dc0-db94-47f2-b7ad-b3ea866a2a10.jpg?v=1784082743","url":"https:\/\/www.spareoil.com\/products\/yokogawa-aat141-s00-centum-analog-input-module","provider":"SpareOil Automation","version":"1.0","type":"link"}