100 % original. Más de 100 000 piezas en stock. Listas para enviar.

  • es

Schneider Electric 140DDO15310 Modicon Quantum Module

Configured for discrete signaling and control over physical output components in Modicon Quantum automation platform networks, the Schneider Electric 140DDO15310 (140DDO15310 TTL Discrete Output Module) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model 140DDO15310
Brand Schneider Electric
Origin Technical data not specified
Weight 0.45 kg (0.99 lb)
Dimensions Standard module format
Operating Temp 0 to 60 deg C
Power Consumption 4 W power dissipation (Bus current requirement: 350 mA @ 5 V DC; Current consumption: 2800 mA @ 5 V DC)
Discrete Output Number 32 channels (4 groups of 8 channels)
Discrete Output Type Positive (sink), TTL level
Discrete Output Voltage 5 V DC (4 to 5.5 V DC rated supply voltage)
Voltage State 1 Guaranteed <= 0.2 V
Internal Pull-up Resistor 440 Ohm
Maximum Load Current <= 75 mA each point; <= 600 mA each group; <= 2.4 A per module
Response Time <= 250 us (state 0 to state 1 and state 1 to state 0 resistive)
Isolation Between Groups 500 Vrms for 1 minute
Circuit Protection Transient voltage suppression (TVS); internal fuse protection
Fault Indication Loss of field power; blown fuse

Industrial PLC Control & Drive Networks Properties

Operating inside the Modicon Quantum hardware architecture, this high-density module utilizes specific backplane bus communication velocity parameters to drive 32 channels of low-voltage TTL logic. The system scales local I/O density scaling profiles by grouping channels into four independent branches, minimizing electrical cross-talk and thermal load during high-frequency switching operations. The design maintains direct firmware flash compatibility with Quantum processors, executing fast <= 250 us response thresholds over Profinet / EtherNet/IP deterministic networks to manage machine sequencing and real-time interlocking routines without injecting loop latency.

Frequently Asked Questions

Q: What specific field-side faults can the 140DDO15310 hardware detect and report to the processor?

A: The onboard diagnostic circuitry continuously monitors the electrical state of the output subassembly, triggering register flags and a red faceplate fault LED upon detecting either a loss of external field power or an internal blown fuse condition.

Q: What are the peak surge current and absolute voltage limits that the output circuit can tolerate?

A: Each individual point handles a peak surge current of 750 A for 0.5 ms. The absolute maximum output limit is rated at 15 V DC for a decaying voltage pulse lasting no longer than 1.3 ms.

Q: How is galvanic isolation structured across the 32 discrete TTL channels?

A: The module separates the channels into four distinct groups of eight. Internal optocouplers enforce an electrical isolation boundary of 500 Vrms for 1 minute between these independent channel groups.

Field Installation Guidelines

Insert the 140DDO15310 module into its assigned slot on the Modicon Quantum backplane rack, confirming that the backplane connectors seat completely before locking the module retention clips. Wire the 5 V DC external TTL logic circuits to the field terminal block, observing the positive sink configuration requirements. Keep the total load current below 600 mA per channel group and 75 mA per individual point to prevent triggering the internal fuse protection. Route all low-voltage TTL signal runs in separate, shielded wire paths away from high-voltage AC power lines and industrial variable speed drive cables to prevent inductive noise from causing premature state changes.