100 % original. Más de 100 000 piezas en stock. Listas para enviar.

  • es

Yokogawa ADV141-P53 Digital Input Module

Configured for high-voltage 100 to 120 VAC discrete signal acquisition in CENTUM VP control systems, the Yokogawa ADV141-P53 (ADV141 Digital Input Module) provides direct physical/electrical execution.

Suffix Breakdown & Model Matrix

Code / Suffix Description Technical Implication
ADV141 Base Hardware Model 16-channel isolated digital input module (100 to 120 VAC nominal)
-P Pushbutton Input Option Enables direct pushbutton edge detection and contact monitoring
5 Display & Non-Ex Type Includes front-panel status LEDs; non-explosion-proof specification
3 Environmental & Temp Option Includes ISA Standard G3 conformal coating and extended operating range (-20 to 70 deg C)

Hardware Specifications

Parameter Specification
Model ADV141-P53
Brand Yokogawa
Origin Japan
Weight 0.40 kg Net / 2.0 kg Shipping
Dimensions Standard Yokogawa CENTUM VP rack-mount I/O footprint
Operating Temp -20 to +70 deg C
Power Consumption 330 mA at 5 VDC
Input Channels 16 discrete inputs
Signal Type 100 to 120 VAC, 50/60 Hz
Input ON Voltage Range 85 to 132 VAC
Input OFF Voltage <= 30 VAC
Input Current 4.1 mA +/- 20% per channel at nominal voltage
Max Allowable Input Voltage 150 VAC
Isolation Withstand 2000 VAC for 1 minute (signal to system logic)
Response Time <= 8 ms
Conformal Coating ISA Standard G3 compliant

Process Control and DCS Isolation Interface

The module processes discrete high-voltage field contact states across 16 isolated channels, channeling field data straight to node controllers while preventing common-mode ground loops. Incorporating channel-to-system optical isolation up to 2000 VAC withstand rating, the hardware decouples plant-floor electrical transients from sensitive backplane logic. Designed for seamless execution within process control systems, the unit maintains signal integrity across severe industrial environments through ISA Standard G3 environmental protection.

Frequently Asked Questions

Q: Does the ADV141-P53 module allow live hot-swapping during system operation?

A: Yes. You can remove and replace an ADV141-P53 module online while the backplane remains powered, preserving continuous execution across adjacent I/O slots.

Q: How does the module handle signal isolation between field wiring and system backplane?

A: The module uses galvanic and optical isolation barriers that withstand 2000 VAC for one minute, isolating field-side AC noise and ground potential differences from system logic.

Q: What environmental conditions does the "-P53" suffix configuration protect against?

A: The suffix designates an extended operating temperature range of -20 to 70 deg C alongside ISA Standard G3 conformal coating, which shields internal circuitry from corrosive atmospheric contaminants.

Field Installation Guidelines

  • Mounting and Latch Verification: Slide the module firmly into its assigned slot on the node unit baseplate until top and bottom retention mechanism levers lock completely into place.
  • Grounding and Shielding Protocols: Connect cabinet structure earth to the primary copper ground bus before applying field voltage. Ensure field wiring metal conduits terminate at the designated cabinet entry ground plate.
  • AC Field Wiring Separation: Route 100-120 VAC input signal cables through dedicated wire troughs strictly separated from low-voltage DC lines and high-speed communication buses to suppress capacitive coupling.