100 % original. Más de 100 000 piezas en stock. Listas para enviar.

  • es

Schneider Electric BMXDDO1602 Modicon X80 Discrete Output Module

Configured for precise binary electrical execution in Modicon X80 platforms, the Schneider Electric BMXDDO1602 (BMX-DDO-1602 Discrete Output Module) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model BMX-DDO-1602
Brand Schneider Electric
Product Type Discrete Output Module
Origin France
Weight 0.12 kg
Dimensions 32 mm x 100 mm x 86 mm
Operating Temp 0 to 60 deg C
Power Consumption Max current per module 10 A
Channel Density 16 discrete channels
Discrete Output Logic Positive (Source)
Output Voltage 24 VDC
Current per Channel 0.625 A
Maximum Voltage Drop <1.2 V at state 1
Response Time on Output 1.2 ms
Insulation Resistance > 10 MOhm 500 VDC
MTBF Reliability 410000 H

Industrial Control & I/O Density Scaling

The module dictates logic command transfer across the rack chassis while interfacing directly with Modicon M340 and M580 PAC platforms. During high-density I/O density scaling routines, the hardware preserves deterministic backplane bus communication velocity by maintaining stable physical execution profiles. Internal reverse mounted diodes deliver continuous reverse polarity protection, while dedicated diagnostic thresholds detect preactuator faults below 14 VDC to prevent false signaling states from interrupting core industrial control tasks.

Frequently Asked Questions

Q: What are the electrical constraints regarding paralleling outputs on the BMXDDO1602?

A: Paralleling of outputs is permitted to support higher current demands, restricted to a maximum of 2 channels. Connecting more than 2 outputs in parallel violates thermal boundary limits and risks permanent damage to the internal transistor arrays.

Q: Is this module equipped with galvanic isolation between individual channels?

A: No, the 16 output channels share a common ground reference. The hardware provides 1400 VDC isolation strictly from channel-to-bus to protect the central backplane architecture, but it does not incorporate channel-to-channel isolation.

Field Installation Guidelines

  1. Power down the Modicon X80 rack power supply and all external 24 VDC preactuator power loops before mounting the hardware.
  2. Slot the module housing into the standard X80 rack chassis connector, ensuring the lower structural hook engages completely before pivoting the top into place.
  3. Fasten the integrated module retention screw to secure the unit against the metal grounding plane of the rack assembly.
  4. Verify that external fuses are installed to supplement the internal short-circuit, overload, and overvoltage protection circuits against high-energy field faults.
  5. Maintain separate routing paths for the discrete output signal lines and heavy motor supply cabling to eliminate inductive noise cross-coupling inside the enclosure.