100 % original. Más de 100 000 piezas en stock. Listas para enviar.

  • es

YOKOGAWA AAI841-H00 Analog I/O Module

The YOKOGAWA AAI841-H00, also cataloged as the AAI841 Analog I/O Module, operates as a dedicated hardware component for simultaneous 8-channel analog input and 8-channel analog output execution within CENTUM VP process control platforms.

Suffix Breakdown & Model Matrix

  • AAI841: Base model for 8-channel analog input/8-channel analog output (4-20 mA).
  • -H: Indicates support for digital communication via HART protocol.
  • 00: Standard base version.
  • K4A00: Option code representing the inclusion of the ATK4A-00 KS cable interface adapter for system cabling.

Hardware Specifications

Parameter Specification
Model AAI841-H00
Brand YOKOGAWA
Origin Japan
Weight 0.3 kg (Module), 2.0 kg (Total shipping weight)
Dimensions Standard I/O module footprint
Operating Temp -20 deg C to 70 deg C
Power Consumption 310 mA (5 VDC), 500 mA (24 VDC)
I/O Channels 8 Inputs / 8 Outputs (non-isolated)
Output Load 0 to 750 Ohm
Accuracy Input: +/-16 uA, Output: +/-48 uA
Data Update Period 10 ms

DCS Process Control & Connectivity

The AAI841 utilizes the 4-20 mA HART loop protocol to manage bidirectional communication with smart field instruments. The module executes precise loop control by maintaining a consistent 40 ms output step response and 100 ms input step response. Given the non-isolated circuit design, the module manages common-mode voltage fluctuations through high-impedance input stages (min 500 kOhm power-off resistance). Furthermore, the internal logic provides active transmitter power supply regulation, maintaining between 14.8 VDC and 26.4 VDC, which allows for selectable 2-wire or 4-wire transmitter compatibility on a per-channel basis.

Frequently Asked Questions (FAQ)

Q: Does the AAI841-H00 support online module replacement (hot-swap)?

A: Yes, the module supports hot-swapping when configured within a dual-redundant pair to maintain process continuity.

Q: How does the module handle circuit-open conditions?

A: The AAI841 includes integrated diagnostic circuitry that triggers an open-circuit fault flag when output current drops below 0.65 mA.

Field Installation Guidelines

  • Grounding: Because the AAI841 channels are non-isolated, ensure that all signal commons are bonded to a common instrument ground bar to prevent circulating currents that could induce measurement offsets.
  • Shielding: Use shielded twisted-pair cabling for all analog signal runs. Terminate cable shields strictly at the field side or the cabinet entry point, but avoid ground loops by maintaining a single-point connection.
  • Thermal Management: Maintain a minimum clearance of 50 mm above and below the module to facilitate vertical airflow. In high-density cabinets, utilize forced ventilation to keep ambient temperatures below the 70 deg C limit.
  • Wiring Interface: When using the ATK4A-00 adapter, ensure all MIL connector latches are fully engaged and locked to prevent intermittent signal loss due to vibration or thermal expansion.