100 % original. Más de 100 000 piezas en stock. Listas para enviar.

  • es

Yokogawa AFV10D-S41101 Duplexed Field Control Unit

Configured for deterministic control logic execution in CENTUM VP platforms, the Yokogawa AFV10D-S41101 (AFV10D Field Control Unit) provides direct hardware-level integration for regulatory and sequence control tasks via Vnet/IP communication networks.

Suffix Breakdown & Model Matrix

The AFV10D series utilizes specific suffix codes to define redundancy architecture, power input requirements, and environmental protection levels.

Model Suffix Specification Details
AFV10D-S Standard Field Control Unit type
4 Dual-Redundant Vnet/IP, Dual-Redundant power supply
1 Always 1 (Reserved)
1 100-120 VAC power supply
0 Basic type
1 LFS1500 Control Function for FIO nodes

Hardware Specifications

Parameter Specification
Model AFV10D-S41101
Brand Yokogawa
Origin Japan (Manufacturing origin)
Weight 6.0 kg to 8.0 kg (Config dependent)
Dimensions 350 x 260 x 180 mm
Operating Temp 0 deg C to +55 deg C
Power Consumption 200 VA
Interface Vnet/IP and FIO node support

Process Control & Network Connectivity

The unit facilitates process control through high-speed deterministic scan cycles, managing I/O signals from connected FIO node units. The architecture supports full duplexing of both processor and power supply modules, ensuring seamless failover without interrupting the control logic execution. This controller implements channel-to-channel isolation on the I/O bus interface to mitigate electrical interference from field wiring. Integrated diagnostic routines perform continuous monitoring of the control environment, including cold junction compensation (CJC) for analog measurement circuits, ensuring that precision is maintained regardless of internal thermal variations or localized noise.

Frequently Asked Questions (FAQ)

Q: Does the AFV10D-S41101 support online hardware replacement?

A: Yes, the unit is engineered for online maintenance. Redundant CPU and power modules can be extracted and replaced while the control station remains energized, provided the redundancy handshake remains active between the primary and standby modules.

Q: Can this unit handle legacy communication interfaces?

A: The AFV10D-S41101 is specifically designed for Vnet/IP network architectures and FIO node communication. Ensure that all field network components are compliant with Vnet/IP protocols to prevent packet loss or communication timing jitter.

Field Installation Guidelines

  • Mounting: Secure the baseplate (A2BE1D/A2BE2D) to the cabinet frame using standard M5 hardware. Confirm the mounting surface is flat to prevent structural stress on the backplane connector pins.
  • Grounding: Bond the cabinet frame to the protective earth (PE) bus using a low-impedance copper strap. This connection is necessary for the integrity of the internal surge protection and noise immunity circuits.
  • Cabling: Utilize shielded twisted-pair cabling for all FIO node connections. Route these cables through dedicated signal wireways, maintaining a minimum separation of 150 mm from high-voltage AC power lines to avoid induced noise.
  • Verification: Upon installation, check the status LED indicators on the front panel. A steady green state on the system bus indicators confirms correct synchronization between the redundant processors and the Vnet/IP network.

¿Qué dicen nuestros clientes sobre nosotros?