The Yokogawa AFV30D-A41252, also cataloged as the AFV30D Field Control Unit, operates as a dedicated hardware component for process control logic execution and real-time database management within CENTUM VP DCS platforms.
| Parameter | Specification |
|---|---|
| Model | AFV30D-A41252 |
| Brand | Yokogawa |
| Origin | Japan |
| Weight | 8.0 kg (Shipping weight: 9.0 kg) |
| Dimensions | Standard 19-inch rack mountable (4U height profile) |
| Operating Temp | 0 deg C to +60 deg C |
| Power Consumption | Approximately 230 VA (220-240 V AC) |
| Network Interface | Dual-redundant Vnet/IP (1 Gbps deterministic Ethernet) |
| Processor Engine | Supports CP471 processor module |
| Memory Backup | Battery-backed main memory up to 72 hours |
| READY Output | Dry contact, 30 V DC, maximum 0.3 A rating |
| Ingress Protection | IP20 (must be housed in an enclosure) |
The AFV30D-A41252 incorporates a dual-redundant architecture utilizing dual CP471 processor modules operating in a hot-standby configuration. Bus communication is sustained via dual-redundant Vnet/IP networks, providing high-bandwidth, deterministic control loop coordination. Real-time control execution tasks communicate directly with FIO modules across dedicated ESB bus interfaces. For process loop reliability, the unit does not deploy channel-to-channel isolation internally but relies on the galvanic isolation barriers of the connected FIO modules. Diagnostic routines monitor temperature levels and processor synchronicity, activating the dedicated READY dry contact in the event of an hardware fault.
Q: How is memory protected during a complete loss of utility power?
A: The AFV30D-A41252 includes an onboard backup battery assembly. Upon loss of external 220-240 V AC supply, the database and active control states are retained in the volatile memory of the CP471 processor modules for up to 72 hours.
Q: What network infrastructure is required to connect the duplexed Vnet/IP interfaces?
A: Connection requires standard UTP Category 5e or higher cabling linked to dedicated Vnet/IP layer 2 control switches. Both Vnet/IP domains (Bus 1 and Bus 2) must be wired independently to preserve complete fault-tolerant redundancy.
Q: Can this standard unit be installed directly in Class 1 Div 2 or Zone 2 locations?
A: No. The suffix code "5" designates a basic type without intrinsic safety or specialized explosion protection. For hazardous environments, the module must be installed inside a sealed, purged, or certified flameproof enclosure with external signal isolation.