100 % original. Más de 100 000 piezas en stock. Listas para enviar.

  • es

Yokogawa SDV544-S23 Safety Digital Output Module

Configured for high-integrity actuator command execution in ProSafe-RS platforms, the Yokogawa SDV544-S23 (SDV544 Safety Digital Output Module) provides direct physical/electrical execution across 24 VDC field control loops.

Hardware Specifications

Parameter Specification
Model SDV544-S23 (Base Model: SDV544)
Brand Yokogawa Electric Corporation
Origin Japan
Weight 0.4 kg
Dimensions 32 x 127 x 127 mm
Operating Temp 0 deg C to +60 deg C
Power Consumption 450 mA at 5 VDC backplane supply / 150 mA at 24 VDC external supply
Output Channels 16 channels (isolated)
Rated Output Voltage 24 VDC (external loop power required)
Maximum Load Current 0.6 A per channel (8 A total aggregate module load)
Safety Compliance SIL3 (IEC 61508 certified)
Isolation Voltage 1500 VAC between output logic and system backplane for 1 minute
Response Time 40 ms maximum (logic command to output transition)

Process Control and Signal Isolation Features

The SDV544-S23 executes safe state de-energization for solenoid valves, trip relays, and alarm indicators. Each channel relies on internal galvanic channel-to-system isolation to suppress ground loop current and prevent external field voltage surges from damaging central processing units. Furthermore, active pulse-test diagnostic routines continuously verify internal switching transistors and field wiring loop continuity without disturbing connected inductive loads. Under nominal operating conditions, clean 24 VDC loop distribution maintains high noise rejection across long field runs, ensuring accurate actuation times during critical shutdown sequences.

Frequently Asked Questions

Q: Does replacing an SDV544-S23 module require shutting down the entire ProSafe-RS node?

A: Maintenance teams can hot-swap the SDV544-S23 online while the safety node remains powered, provided the system runs a dual-redundant I/O configuration. The active secondary module assumes loop control during the exchange process.

Q: How does internal pulse testing prevent false trips on connected solenoid valves?

A: The module injects microsecond-duration off-pulses into the output circuit to evaluate switching response. Because the pulse duration is significantly shorter than the mechanical response threshold of standard relays and solenoids, the field device remains continuously energized during diagnostic execution.

Field Installation Guidelines

Mount the SDV544-S23 vertically into an assigned slot of an FIO safety node unit inside a IP54-rated control enclosure. Connect external 24 VDC field wiring to the pressure clamp terminal block or dedicated signal cable adapter. Technicians must route low-voltage 24 VDC output conductors separately from high-voltage AC lines to prevent inductive coupling. Connect the primary cabinet grounding strap directly to the earth bar and ensure the external 24 VDC field power supply floats relative to protective earth to maximize system noise immunity.