100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

Product Description

The Allen-Bradley 1794-IT8 is a high-resolution thermocouple and millivolt input module for the FLEX I/O platform. It provides eight independently configurable differential input channels, supporting a wide range of thermocouple types as well as direct millivolt signals for precise temperature measurement.

Using a 16-bit A/D converter, the 1794-IT8 delivers high accuracy for critical thermal monitoring. Integrated cold junction compensation (CJC) support and open-wire detection ensure reliable data acquisition, even in harsh industrial environments. Its modular FLEX I/O design allows I/O to be installed close to field sensors, reducing wiring complexity, cabinet space, and installation costs.


Technical Specifications

Parameter Description
Model Number 1794-IT8
Input Channels 8 differential
Supported Inputs Thermocouple or millivolt
Nominal Input Range −76.5 mV to +76.5 mV
Resolution 16-bit (≈ 2.384 μV/LSB)
Data Formats 16-bit 2’s complement or Offset Binary
Channel Bandwidth 0 to 2.62 Hz (−3 dB)
Isolation Voltage 850 V DC (1 s, inputs/user power to logic)
Flexbus Current 20 mA
Power Dissipation Max. 3.0 W @ 31.2 V DC
Thermal Dissipation Max. 10.2 BTU/hr
Status Indicators 1 Red/Green LED (Power & Health)
Compatible Terminal Bases 1794-TB2, 1794-TB3, 1794-TB3T
Dimensions (W × H × D) 45.7 × 94.0 × 53.3 mm

Typical Applications

  • Process Temperature Monitoring
    Accurate sensing in reactors, furnaces, kilns, and heat exchangers.

  • Skid-Mounted Systems
    Distributed temperature inputs close to sensors using FLEX I/O.

  • Energy & Utilities
    Boiler, turbine, and exhaust temperature monitoring.

  • OEM Equipment
    Compact, high-density temperature acquisition in packaged machinery.


Technical FAQ

Q: Does the 1794-IT8 require a separate CJC sensor?
A: Yes. Accurate thermocouple measurement requires a CJC-enabled terminal base, such as the 1794-TB3T, to compensate for ambient connection temperature.

Q: What happens if a thermocouple wire breaks?
A: The module provides open-circuit detection. When a break is detected, the channel drives to a predefined fault value (typically full scale) to alert the controller.

Q: Can different thermocouple types be mixed on one module?
A: Yes. Each channel is independently configurable in the controller software for its specific thermocouple type or millivolt range.

What's clients say about us