100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

Product Description

The 8C-PAIN01 (Spare P/N: 51454356-175) is a premium differential analog input module engineered for the Honeywell Experion PKS Series 8 platform. It is specifically designed for high-precision signal acquisition, featuring 1000 VDC optical isolation to safeguard control logic from field-side electrical surges and ground loops.

Unlike standard single-ended input modules, the 8C-PAIN01 employs high-impedance differential voltage inputs, providing excellent common-mode noise rejection in electrically noisy industrial environments. It supports a wide variety of signal types, including bi-directional current and standard voltage loops, making it ideal for complex process monitoring in industries such as power generation and refining.


Technical Specifications

Item Specification
Model Designation 8C-PAIN01
Part / Spare Number 51454356-175
Input Architecture High-impedance differential voltage, optically isolated
Isolation Rating 1000 VDC
Configurable Input Ranges −40 to +40 mA, 0–20 mA, 0–10 V
Input Impedance > 10 MΩ
Conversion Accuracy ±0.1% of Full Scale
Signal Resolution 0.01% of Full Scale
Common Mode Rejection > 120 dB @ 60 Hz
Overload Protection 120% (2 s) / 150% (0.1 s) of Full Scale
Dimensions (W×H×D) 5.1 × 26.7 × 17.8 cm
Net Weight 0.5 kg

Application Context

The 8C-PAIN01 is ideal for applications where signal integrity is critical, including:

  • Monitoring high-voltage battery arrays

  • Measuring small voltage drops across shunt resistors

  • Precision analog loops in power plants and refineries

Its 1000 V isolation ensures that even in the event of a field-side fault, the C300 controller remains protected.


Frequently Asked Questions

Q: What is the benefit of the differential input on the 8C-PAIN01?
A: The differential design measures the voltage difference between two points while rejecting common-mode voltage, greatly reducing EMI and noise errors.

Q: Does the 8C-PAIN01 support 4–20 mA loops?
A: Yes. The module can be configured for 0–20 mA or −40 to +40 mA, covering standard industrial 4–20 mA instrumentation.

What's clients say about us