Configured for converting signals from magnetic flow tubes into standardized outputs within process automation networks, the Yokogawa AMM31, also cataloged as the AMM31 Magnetic Flow Converter, provides direct physical/electrical execution.
| Parameter | Specification |
|---|---|
| Model | AMM31 |
| Brand | Yokogawa |
| Origin | Japan |
| Weight | 0.2 kg (6.1 oz) |
| Dimensions | 12.7 cm x 2.5 cm x 20.3 cm |
| Operating Temp | Standard industrial range |
| Power Consumption | Configured per excitation protocol requirements |
| Excitation Method | Dual frequency (up to 400 mm tube) / Pulsed DC (500 mm and larger) |
| Response Time | 0.1 s |
| Current Output | 4-20 mA DC (max. 1000 Ohm load) |
| Pulse Output | Transistor contact, 30 VDC (OFF), 200 mA (ON), 0.0001-1000 pps |
| Alarm Output | Transistor contact, 30 VDC (OFF), 200 mA (ON) |
| Status Output | 2 x Transistor contacts, 30 VDC (OFF), 200 mA (ON) |
| Communication Protocols | BRAIN / HART |
| Cable Length Limit | Up to 2 km via PVC-sheathed control cables |
| Enclosure Protection | NEMA 4 equivalent |
| Case Material | Aluminum alloy with polyurethane corrosion-resistant coating |
| Mounting Options | 2-inch pipe, panel, or surface mount |
| Grounding Resistance | 100 Ohm maximum (10 Ohm maximum when utilizing surge arrestor function) |
| Data Storage | Non-volatile EEPROM (no backup battery required) |
The module utilizes a 4-20 mA HART loop protocol alongside the proprietary BRAIN communication layer to interface directly with distributed control system (DCS) architectures. To preserve signal integrity across long-distance topologies up to 2 km, the hardware maintains independent channel-to-channel isolation parameters between the primary flow tube excitation circuit and the analog/pulse output terminals. Signal processing functions leverage dual-frequency excitation techniques to suppress slurry noise and fluid hydrodynamic variations, executing real-time digital filtering without introducing phase lag into the 4-20 mA control loop.
Q: What are the specific load resistance boundaries for establishing digital communication with the AMM31?
A: For BRAIN protocol communication, the loop must maintain a load resistance between 250 Ohm and 600 Ohm. For HART protocol configuration, the required loop resistance range is 230 Ohm and 600 Ohm.
Q: How does the unit store calibration and configuration constants during a total power disruption?
A: The device writes all operational parameters, flow tube constants, and multi-range settings directly to an internal EEPROM. This non-volatile storage method eliminates the need for lithium backup batteries and prevents data corruption during prolonged power outages.
Nuestra línea de producción se paró debido a un monitor Bently Nevada defectuoso. Lo encontramos en stock aquí y lo enviaron por DHL de inmediato. Volvió a funcionar en 48 horas, lo que realmente salvó nuestra planta.
Encontrar módulos nuevos y originales es fundamental para nuestra seguridad. Este equipo entrega componentes de fábrica con certificación completa. Su compromiso de vender únicamente productos nuevos los convierte en nuestro socio de mayor confianza.
Llevamos dos años abasteciendo aquí piezas de Honeywell y Schneider. Todos nuestros envíos llegan perfectamente embalados, con los precintos originales de fábrica intactos. Ofrecemos una comunicación clara y los mejores plazos de entrega del sector.