100 % original. Más de 100 000 piezas en stock. Listas para enviar.

  • es

The GE Fanuc IC200UDR164, also cataloged as the IC200UDR164 Micro Controller, operates as a dedicated hardware component for direct signal processing and control loop execution within VersaMax system networks. The unit integrates 40 discrete AC/DC inputs and 24 normally open SPST relay outputs on board, managing 64 total I/O points across the local processing unit.

Hardware Specifications

Parameter Specification
Model IC200UDR164
Brand GE Fanuc
Origin USA
Weight 2.00 lbs (0.91 kg)
Dimensions Compact VersaMax Micro footprint
Operating Temp 0 deg C to 60 deg C
Power Consumption 100-240 VAC input voltage range (50-60 Hz)
Onboard I/O Points 64 points (40 Inputs / 24 Outputs)
Output Type Normally Open Relay Outputs (SPST)
Contact Rating 2 A maximum resistive load at 24 VDC and 240 VAC
Input Logic Configurable positive or negative logic
Holdup Time 10 ms at 85-100 VAC; 20 ms at 100-265 VAC
Maximum Inrush Current 30 A at 200 VAC; 40 A at 265 VAC

Backplane Bus Communication Velocity & Firmware Flash Compatibility

The microcontroller unit coordinates data transfers across internal expansion buses to execute local logic cycles and manage field device signals. High-density I/O handling is maintained via 40 input circuits supporting selectable positive or negative logic polarities. Firmware flash compatibility within the unit ensures real-time synchronicity during execution cycles, maintaining system data integrity during brief line power disruptions via onboard holdup capacitors rated up to 20 ms at nominal operating voltages.

Frequently Asked Questions

Q: What are the contact output specs and limits for the IC200UDR164?

A: The onboard output section provides 24 SPST normally open relay contacts, rated for a maximum resistive load of 2 A per channel at either 24 VDC or 240 VAC.

Q: What input power source is required to operate the microcontroller?

A: The module operates directly from an AC line voltage ranging from 100 VAC to 240 VAC at 50 to 60 Hz.

Q: How long can the unit maintain operation during an AC mains voltage dip?

A: The internal power supply provides a holdup time of 10 ms for line voltages between 85-100 VAC and up to 20 ms for voltages between 100-265 VAC.

Field Installation Guidelines

  1. Mount the unit securely onto a standard 35 mm DIN rail or fasten it directly to an electrical enclosure backpanel using mounting hardware.
  2. Wire incoming AC supply lines (100-240 VAC) to the dedicated line, neutral, and ground input terminals.
  3. Ensure inductive field loads connected to the relay output channels feature proper RC snubbers or flyback diodes to prevent arc erosion on the SPST contacts.
  4. Ground the controller frame to the main enclosure earth ground terminal using heavy-gauge copper conductor.
  5. Verify that inrush current limits are accounted for in power distribution protection design (up to 40 A at 265 VAC).