The Schneider Electric 140XCA71706 serves as the primary 140XCA71706 Backplane Expander Cable utilized to execute rack-to-rack communication across Modicon Quantum automation platform networks.
| Parameter | Specification |
|---|---|
| Model | 140XCA71706 |
| Brand | Schneider Electric |
| Origin | Technical data not specified |
| Weight | 0.2 kg Net (Shipping Weight: 1.5 kg) |
| Dimensions | Cable length: 2 m (6.56 ft) |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | Technical data not specified (Passive conductor system) |
| Product Type | Backplane expander cable |
| Compatible Modules | 140XBE10000 backplane expander modules |
| Connector Type | PROFIBUS-type connectors at both ends |
| Jacket Material | Industrial-grade PVC |
| Operating Humidity | Up to 80% RH (non-condensing) |
| Altitude Rating | Up to 1000 m |
| Ingress Protection | IP20 |
| Environmental Status | Green Premium, RoHS-compliant, mercury-free |
Operating inside the Modicon Quantum hardware architecture, this 2 m interconnection cable links primary and expansion chassis via 140XBE10000 expander modules to maintain standard backplane bus communication velocity. The internal conductor arrangement uses specific shielding layers to minimize industrial electromagnetic and radio frequency interference (EMI/RFI), preserving data frame accuracy across Profinet / EtherNet/IP deterministic networks. The heavy-duty jacket profile and PROFIBUS-type connector interfaces enforce direct firmware flash compatibility by securing the high-speed bus links against micro-disconnections, sustaining target system I/O density scaling profiles without latency.
Q: What specific hardware modules are required to interface with the 140XCA71706 bus cable?
A: This cable is engineered to plug directly into the 140XBE10000 backplane expander modules, establishing the physical link between the main CPU rack and the secondary expansion rack.
Q: Does the cable shield provide protection against grounding loops across different racks?
A: The cable provides industrial-grade continuous shielding to suppress high-frequency noise and EMI. To prevent ground loops, both interconnected backplane chassis must be bonded to the same low-impedance master enclosure instrument ground bar.
Q: Can this cable be altered or extended past its factory 2 m length limit?
A: No. The cable length and internal impedance profiles are tuned to prevent signal reflections and propagation delays. Altering the 2 m physical length will corrupt high-speed backplane bus integrity.
Isolate the electrical power supplying both Quantum backplane racks before connecting the expansion link. Align the PROFIBUS-type connector on the 140XCA71706 cable with the port on the first 140XBE10000 module, seating it completely, and engage the integrated locking screws to ensure a continuous mechanical ground connection. Route the 2 m cable body through designated panel wire trays, keeping it clear of high-current AC power cables, variable speed drive links, and thermal sources. Connect the opposite end to the destination rack expander module using the same locking procedure, making sure not to exceed the maximum bending radius of the industrial PVC jacket during final cable placement.
Nuestra línea de producción se paró debido a un monitor Bently Nevada defectuoso. Lo encontramos en stock aquí y lo enviaron por DHL de inmediato. Volvió a funcionar en 48 horas, lo que realmente salvó nuestra planta.
Encontrar módulos nuevos y originales es fundamental para nuestra seguridad. Este equipo entrega componentes de fábrica con certificación completa. Su compromiso de vender únicamente productos nuevos los convierte en nuestro socio de mayor confianza.
Llevamos dos años abasteciendo aquí piezas de Honeywell y Schneider. Todos nuestros envíos llegan perfectamente embalados, con los precintos originales de fábrica intactos. Ofrecemos una comunicación clara y los mejores plazos de entrega del sector.