The Yokogawa YS150-012/A31 S3, also cataloged as the YS150 Single-Loop Programmable Controller, operates as a dedicated hardware component for precise closed-loop PID control execution within YS100 series architectures.
The suffix alphanumeric codes specify hardware options and firmware build levels:
| Parameter | Specification |
|---|---|
| Model | YS150-012/A31 S3 |
| Brand | Yokogawa |
| Origin | Japan |
| Weight | 1.2 kg to 1.5 kg |
| Dimensions | 96 x 96 x 150 mm (or 144 x 144 x 150 mm DIN panel footprint) |
| Operating Temp | 0 deg C to +50 deg C |
| Storage Temp | -20 deg C to +70 deg C |
| Power Consumption | 20 VA |
| Control Loops | 1 loop (single-loop controller) |
| Sampling Period | 100 ms |
| Control Algorithm | PID with auto-tuning, manual tuning, and fuzzy logic overshoot suppression |
| Input Types | Universal: Thermocouple, RTD, DC voltage (1-5 V), DC current (4-20 mA) |
| Input Accuracy | +/-0.1% of span |
| Analog Outputs | 1 channel; 4-20 mA DC or 1-5 V |
| Digital I/O | 4 digital input points, 2 digital relay output points |
| Communication | RS-485 interface supporting Modbus RTU protocol |
| Power Supply | 100-240 VAC (50/60 Hz) |
| Mounting | Panel mount |
The controller incorporates hardware signal isolation between input, output, and power supply terminals to prevent ground loops and protect against high-voltage field line transients. The analog front-end processes inputs with a 100 ms sampling period, executing digital filtering and cold junction compensation (CJC) for connected thermocouple sensors. Operating over a 4-20 mA HART or standard analog loop topology, the internal output converter translates real-time PID algorithm calculations into continuous control signals with 0.1% span accuracy.
Q: What communication protocols does the YS150-012/A31 S3 support for DCS integration? A: The onboard RS-485 serial port supports the Modbus RTU protocol, enabling bidirectional communication with master PLCs or DCS host platforms.
Q: How does the unit process cold junction compensation during thermocouple operation? A: Internal CJC circuits measure local terminal temperature directly, adjusting raw millivolt thermocouple signals before PID processing to maintain input conversion accuracy of +/-0.1% of span.
Q: What input signals can connect directly to the universal input terminals? A: The universal input accepts thermocouples, RTDs, 1-5 V DC voltage, and 4-20 mA DC current signals without requiring external signal conversion cards.
Prepare a square panel cutout corresponding to the DIN standard dimensions and slide the controller unit through the front cutout. Fasten the panel-mount retaining brackets from the rear, tightening mounting screws evenly to form a secure seal against the panel face. Route 100-240 VAC power cables separately from low-level analog input wiring to suppress electro-magnetic induction. Connect thermocouple or 4-20 mA shielded cabling to the rear screw terminals, bonding the cable shield to the central enclosure earth ground at a single end. Ensure that external conduit fittings maintain a minimum engagement of 5 full NPT threads where rigid metal conduits connect to field enclosures.
Nuestra línea de producción se paró debido a un monitor Bently Nevada defectuoso. Lo encontramos en stock aquí y lo enviaron por DHL de inmediato. Volvió a funcionar en 48 horas, lo que realmente salvó nuestra planta.
Encontrar módulos nuevos y originales es fundamental para nuestra seguridad. Este equipo entrega componentes de fábrica con certificación completa. Su compromiso de vender únicamente productos nuevos los convierte en nuestro socio de mayor confianza.
Llevamos dos años abasteciendo aquí piezas de Honeywell y Schneider. Todos nuestros envíos llegan perfectamente embalados, con los precintos originales de fábrica intactos. Ofrecemos una comunicación clara y los mejores plazos de entrega del sector.