The Allen-Bradley 1794-IT8 is a high-resolution thermocouple and millivolt input module for the FLEX I/O platform. It provides eight independently configurable differential input channels, supporting a wide range of thermocouple types as well as direct millivolt signals for precise temperature measurement.
Using a 16-bit A/D converter, the 1794-IT8 delivers high accuracy for critical thermal monitoring. Integrated cold junction compensation (CJC) support and open-wire detection ensure reliable data acquisition, even in harsh industrial environments. Its modular FLEX I/O design allows I/O to be installed close to field sensors, reducing wiring complexity, cabinet space, and installation costs.
| Parameter | Description |
|---|---|
| Model Number | 1794-IT8 |
| Input Channels | 8 differential |
| Supported Inputs | Thermocouple or millivolt |
| Nominal Input Range | −76.5 mV to +76.5 mV |
| Resolution | 16-bit (≈ 2.384 μV/LSB) |
| Data Formats | 16-bit 2’s complement or Offset Binary |
| Channel Bandwidth | 0 to 2.62 Hz (−3 dB) |
| Isolation Voltage | 850 V DC (1 s, inputs/user power to logic) |
| Flexbus Current | 20 mA |
| Power Dissipation | Max. 3.0 W @ 31.2 V DC |
| Thermal Dissipation | Max. 10.2 BTU/hr |
| Status Indicators | 1 Red/Green LED (Power & Health) |
| Compatible Terminal Bases | 1794-TB2, 1794-TB3, 1794-TB3T |
| Dimensions (W × H × D) | 45.7 × 94.0 × 53.3 mm |
Process Temperature Monitoring
Accurate sensing in reactors, furnaces, kilns, and heat exchangers.
Skid-Mounted Systems
Distributed temperature inputs close to sensors using FLEX I/O.
Energy & Utilities
Boiler, turbine, and exhaust temperature monitoring.
OEM Equipment
Compact, high-density temperature acquisition in packaged machinery.
Q: Does the 1794-IT8 require a separate CJC sensor?
A: Yes. Accurate thermocouple measurement requires a CJC-enabled terminal base, such as the 1794-TB3T, to compensate for ambient connection temperature.
Q: What happens if a thermocouple wire breaks?
A: The module provides open-circuit detection. When a break is detected, the channel drives to a predefined fault value (typically full scale) to alert the controller.
Q: Can different thermocouple types be mixed on one module?
A: Yes. Each channel is independently configurable in the controller software for its specific thermocouple type or millivolt range.
Our production line was down due to a faulty Bently Nevada monitor. We found it in stock here and they shipped it via DHL immediately. Back in operation within 48 hours—truly a lifesaver for our plant.
Finding brand new, original modules is critical for our safety. This team delivers factory-fresh components with full certification. Their commitment to only selling new products makes them our most trusted partner.
We have sourced Honeywell and Schneider parts here for two years. Every shipment arrives well-packaged with original factory seals intact. Clear communication and the best lead times in the industry.