The GE Fanuc IC697PWR724, also cataloged as the IC697PWR724 Power Supply Module, operates as a dedicated hardware component for stable DC voltage distribution and system backplane powering within Series 90-70 VME rack systems.
| Parameter | Specification |
|---|---|
| Model | IC697PWR724 |
| Brand | GE Fanuc Emerson |
| Product Line | Series 90-70 |
| Origin | USA |
| Weight | 2.50 lbs (1.13 kg) |
| Dimensions | Standard Series 90-70 single-slot module width |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 160 Watts |
| Nominal Rated Voltage | 24 VDC |
| Input Voltage Range | 18 to 32 VDC |
| Input Inrush Energy | 22 J maximum |
| Output Power | 90 Watts maximum |
| Output Voltage | +5 VDC, +12 VDC, and -12 VDC |
| Overvoltage Limit | 5 VDC output overvoltage protection limit |
| Ride-Through Time | 10 ms |
| Backplane Compatibility | VME Compatible |
The IC697PWR724 module features dedicated internal power conversion circuitry tailored for high-density Series 90-70 backplane configurations. It delivers regulated +5 VDC logic power alongside auxiliary +12 VDC and -12 VDC rails to feed input/output circuits and processing cards across the backplane bus. System firmware flash compatibility and deterministic backplane communication velocity across the VME architecture rely on low-ripple output voltages during transient load demands. The internal power stage incorporates a controlled input inrush energy circuit rated up to 22 J to mitigate voltage sag on the primary 24 VDC feeder bus during initial system energization.
Q: Can the IC697PWR724 module supply power to expansion racks in a Series 90-70 system?
A: Yes, the IC697PWR724 can provide power to a second rack in single or expansion configurations, provided the combined power drain across all connected rails does not exceed the maximum output limit of 90 Watts.
Q: What is the behavior of the supply during short primary power interruptions?
A: The module maintains a minimum ride-through time of 10 ms under full load conditions, permitting execution of hold-up functions before system power failure logic triggers.
Q: Is hot-swapping permitted for the IC697PWR724 module during backplane operation?
A: No, primary 24 VDC input power must be isolated and the backplane de-energized prior to inserting or removing the power supply module to prevent electrical arcing and backplane bus signal corruption.
Nuestra línea de producción se paró debido a un monitor Bently Nevada defectuoso. Lo encontramos en stock aquí y lo enviaron por DHL de inmediato. Volvió a funcionar en 48 horas, lo que realmente salvó nuestra planta.
Encontrar módulos nuevos y originales es fundamental para nuestra seguridad. Este equipo entrega componentes de fábrica con certificación completa. Su compromiso de vender únicamente productos nuevos los convierte en nuestro socio de mayor confianza.
Llevamos dos años abasteciendo aquí piezas de Honeywell y Schneider. Todos nuestros envíos llegan perfectamente embalados, con los precintos originales de fábrica intactos. Ofrecemos una comunicación clara y los mejores plazos de entrega del sector.