100 % original. Más de 100 000 piezas en stock. Listas para enviar.

  • es

HIMA H15Q-HS B5233-1 HiQuad Central Rack System

The HIMA H15Q-HS B5233-1, also cataloged as the H15Q-HS Central Rack System, operates as a dedicated hardware component for high-integrity safety processing and signal execution within HiQuad safety system platforms. It manages redundant power conversion and system backplane routing, accommodating dual central CPU modules alongside up to 13 I/O modules, two communication cards, and four fan assemblies.

Hardware Specifications

Parameter Specification
Model H15Q-HS B5233-1
Brand HIMA
Origin Germany
Weight 15 kg
Dimensions 19-inch rack format, 5 height units
Operating Temp -25 to +60 deg C
Power Consumption Dual 24 VDC / 5 VDC system power paths
CPU Memory 16 MB RAM capacity
Expansion Capacity Supports up to 13 I/O modules, 2 communication modules, 4 fan modules
Communication Protocols Ethernet, Profibus-DP
Functional Safety Rating SIL3 (IEC 61508), PL e (EN ISO 13849-1), TÜV certified
Diagnostic Monitoring Watchdog circuits, fuse status, and fan monitoring
Mounting Type Standard 19-inch cabinet rack installation

SIL3 Certification & Fail-Safe State Execution

The HIMA H15Q-HS B5233-1 incorporates triple power supply redundancy and dual central CPU architecture to ensure uninterrupted fail-safe state execution in safety-instrumented systems (SIS). The subrack bus provides electrical galvanic isolation across adjacent expansion card slots, preventing localized electrical faults or field line transients from compromising central logic processing.

Integrated hardware watchdog circuits, real-time power supply fuse monitoring, and continuous fan speed sensing deliver instant diagnostic reporting across the backplane. In the event of an I/O card or power sub-module failure, the central rack maintains active system operation without dropping communication over its redundant Ethernet and Profibus-DP network interfaces, fulfilling strict SIL3 requirements according to IEC 61508.

Frequently Asked Questions

Q: Does the HIMA H15Q-HS B5233-1 central rack support online module replacement?

A: Yes. The subrack chassis allows hot-swapping of power supply modules, fan assemblies, and I/O cards while the central rack remains energized, provided system handling procedures are followed.

Q: What power input configuration does the subrack require for operation?

A: The central rack accepts a primary 24 VDC input and distributes redundant 5 VDC logic power across the backplane via triple-redundant power modules (such as F7126 units).

Q: How does the chassis handle thermal management for fully loaded card slots?

A: The subrack incorporates dedicated mounting locations for four fan modules, maintaining continuous forced-air ventilation across the -25 to +60 deg C operating temperature spectrum.

Field Installation Guidelines

Mount the 19-inch subrack assembly into a suitable industrial enclosure using standard rack-mounting hardware. Ensure a minimum vertical clearance of 100 mm above and below the rack frame to allow unimpeded airflow through the internal ventilation channels and fan assemblies.

Connect primary 24 VDC supply lines using short, high-current conductors, and tie system ground lines directly to a low-impedance master earthing bus bar. Route all high-voltage power leads and field I/O wiring through separate wire ducts to prevent electromagnetic noise coupling into sensitive central processor communication buses. Tighten all rack retention screws and terminal blocks before applying power.