Configured for power distribution in Centum VP and ProSafe-RS control platforms, the YOKOGAWA PW482-50 (PW482 Power Supply Module) provides direct physical/electrical execution. This hardware component delivers stabilized DC power to field control units and safety systems, ensuring regulated output voltages of 24 V and 5.1 V within industrial process environments.
| Suffix Code | Specification |
|---|---|
| PW482 | Base Power Supply Module |
| -5 | Standard type, no explosion protection |
| -E | Standard type with explosion protection |
| 0 | Basic type |
| 1 | ISA Standard G3 option (-20 deg C to +70 deg C) |
| -50 | Enhanced variant with dual regulated DC outputs (24 V / 5.1 V) |
| Parameter | Specification |
|---|---|
| Model | PW482-50 |
| Brand | Yokogawa |
| Origin | Japan |
| Weight | 2.0 kg |
| Dimensions | 199.5 mm × 190 mm × 149 mm |
| Operating Temp | -20 deg C to +70 deg C (G3 option) |
| Power Consumption | 230 VA |
| Input Voltage | 220 to 240 V AC ±10% |
| Frequency | 50/60 Hz ±3 Hz |
| Redundancy | Dual-redundant supported (2oo2) |
The PW482-50 utilizes dedicated backplane integration to maintain internal system stability. Unlike general-purpose industrial power supplies, this module features internal channel-to-channel isolation and surge protection specifically calibrated for Yokogawa FCU/FIO/ESB bus architectures. The unit requires specific slot placement (P1-P2) on supported base plates (A2BE1D/A2BE2D) to ensure proper galvanic isolation and backplane bus communication velocity. In dual-redundant configurations, the module manages automatic load sharing and maintains continuous voltage regulation during primary supply failure.
Q: Can the PW482-50 be hot-swapped in a running system?
A: Yes, provided the system backplane supports redundant power configurations. In a dual-redundant setup (two modules installed in P1 and P2), one module may be removed or replaced without interrupting the 24 V / 5.1 V DC output to the field control unit.
Q: What is the primary difference between the base PW482 and the -50 variant?
A: The standard PW482 is designed for generic FCU/FIO unit support. The -50 suffix specifically incorporates dual regulated DC outputs (24 V / 5.1 V) required for ProSafe-RS Safety Control System (SCS) logic solvers.
Nuestra línea de producción se paró debido a un monitor Bently Nevada defectuoso. Lo encontramos en stock aquí y lo enviaron por DHL de inmediato. Volvió a funcionar en 48 horas, lo que realmente salvó nuestra planta.
Encontrar módulos nuevos y originales es fundamental para nuestra seguridad. Este equipo entrega componentes de fábrica con certificación completa. Su compromiso de vender únicamente productos nuevos los convierte en nuestro socio de mayor confianza.
Llevamos dos años abasteciendo aquí piezas de Honeywell y Schneider. Todos nuestros envíos llegan perfectamente embalados, con los precintos originales de fábrica intactos. Ofrecemos una comunicación clara y los mejores plazos de entrega del sector.