100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

HIMA F8652X PES H41q Central Module SIL 3 Safety CPU

Product Overview

The HIMA F8652X is a high-integrity central module designed specifically for the HIMA PES H41q-MS, -HS, and -HRS safety systems. As a core component of the H41q architecture, this module is safety-related and certified for use in applications up to SIL 3 according to IEC 61508. The F8652X utilizes dual clock-synchronized Intel 386EX 32-bit microprocessors to ensure deterministic execution of safety logic. Its architecture is built for maximum fault tolerance, incorporating a dedicated safety watchdog and electrically isolated RS-485 interfaces. This module is essential for managing critical safety functions in emergency shutdown (ESD) and fire and gas (F&G) systems where human life and environmental protection are the highest priority.

Technical Specifications

Detailed technical parameters for the HIMA F8652X central module:

Parameter Specification Details
Model Number F8652X
Manufacturer HIMA Paul Hildebrandt
System Compatibility PES H41q-MS, H41q-HS, H41q-HRS
Safety Integrity Level SIL 3 (IEC 61508)
Microprocessor 2 × Intel 386EX (32-bit)
Clock Frequency 25 MHz
Memory per Processor 1 MB Flash-EPROM (OS/User), 1 MB SRAM (Data)
Communication 2 × RS-485 Serial (Isolated)
Diagnostic Display 4-digit matrix display (selectable info)
Safety Watchdog 24 V, 500 mA output, short-circuit proof
Power Requirements 5 V / 2 A
Space Requirement 8 SU (Standard Units)
Construction 2 European standard PCBs + 1 Diagnostic PCB
Origin Germany

 

What's clients say about us