The Honeywell MU-TAIH13 is a High Level Analog Input Field Termination Assembly (FTA) designed for integration with Honeywell TPS and Experion PKS distributed control systems. This module serves as a critical interface between field instrumentation and the control network, facilitating the conversion of standard industrial signals, including 4-20 mA and 0-10 V, into accurate digital data. Engineered for reliability in demanding environments such as petrochemical plants, power generation facilities, and chemical processing units, the MU-TAIH13 ensures signal integrity and high-availability performance.

Features

  • Supports 16 independent analog input channels for high-density signal processing.
  • Designed for redundant I/O configurations, allowing for seamless failover and parallel operation in critical control loops.
  • Includes dedicated signal conditioning and filtering circuitry for each channel to mitigate cross-talk and noise.
  • Features Type C compression terminal connections to ensure robust, vibration-resistant field wiring.
  • Reduces cabinet footprint by facilitating direct field wiring termination, minimizing the requirement for external marshalling.

Technical Specifications

Model MU-TAIH13
Part Number 51309138-125
Input Channels 16
Signal Types 4-20 mA, 0-10 V
Accuracy Better than 0.1% of full scale
Power Consumption Approximately 8 W
Operating Temperature 0 to 60 deg C
Storage Temperature -40 to 85 deg C
Terminal Type Compression Type C
Mounting Size B

Installation Guidelines

  • Ensure the control system is powered down before installing or removing the FTA to prevent electrical damage or signal disruption.
  • Verify that all field wiring is properly secured in the Type C compression terminals to maintain vibration resistance.
  • Maintain proper grounding practices to ensure effective electrical isolation and signal integrity across all 16 channels.
  • Install in a location with adequate ventilation to maintain operating temperatures within the specified 0-60 deg C range.
  • When deploying in redundant configurations, ensure that both primary and secondary FTAs are correctly addressed and wired according to the system architecture documentation.

FAQ

Is the MU-TAIH13 compatible with Experion PKS systems?
Yes, the MU-TAIH13 is designed specifically for use with Honeywell TPS and Experion PKS distributed control systems.

Does this module support redundant I/O?
Yes, this FTA supports redundant I/O configurations, allowing for dual-module deployment to ensure continuous signal acquisition during hardware failure.

What type of field wiring terminals does this unit use?
This model utilizes Type C compression terminals, which are designed for secure, industrial-grade field connections.