Configured for analog voltage signal processing in Series 90-30 platforms, the GE Fanuc IC693ALG222 (IC693ALG222 Analog Input Module) provides direct physical/electrical execution.
| Parameter | Specification |
|---|---|
| Model | IC693ALG222 |
| Brand | GE Fanuc Emerson |
| Origin | USA |
| Weight | 0.88 lbs (0.40 kg) |
| Dimensions | Single-slot Series 90-30 module width |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 112 mA from +5 VDC backplane bus; 41 mA from isolated +24 VDC supply |
| Input Channel Count | 16 single-ended or 8 differential channels |
| Signal Voltage Ranges | 0 to 10 VDC (unipolar), -10 to +10 VDC (bipolar) |
| Resolution (0 to +10 VDC) | 2.5 mV per count (1 LSB = 2.5 mV) |
| Resolution (-10 to +10 VDC) | 5.0 mV per count (1 LSB = 5.0 mV) |
| Linearity | Less than 1 LSB |
| Absolute Accuracy | +/-0.25% of full scale at 25 deg C; +/-0.5% over full operating temp |
| Update Rate | 6 ms per channel (single-ended); 3 ms per channel (differential); 13 ms total scan |
| Input Filter Response | 41 Hz (single-ended mode); 82 Hz (differential mode) |
| Isolation Voltage | 1500 V RMS field to logic side |
| Status Indicators | 2 green LEDs ("Module OK" and "Power Supply OK") |
The IC693ALG222 updates digitized 12-bit voltage representations directly to the CPU logic memory table via the backplane bus. Designed to optimize backplane bus communication velocity and I/O density scaling, it converts unipolar (0 to 10 VDC) or bipolar (-10 to +10 VDC) analog inputs across up to 16 channels in a single rack slot. Firmware flash compatibility supports automated rack scanning with channel update times down to 3 ms in differential mode and 6 ms in single-ended mode. The field-to-logic interface maintains 1500 V RMS isolation to prevent noise propagation across the backplane.
Q: What are the backplane current draw requirements for the IC693ALG222?
A: The module draws 112 mA from the +5 VDC backplane bus for internal logic and 41 mA from the isolated +24 VDC backplane supply to power onboard field-side converters.
Q: What system CPU limits exist for installing multiple IC693ALG222 modules?
A: A maximum of 4 modules can be installed with CPUs 311, 313, or 323; 8 modules with CPU331 or CPU351; 12 modules with CPUs 340/341; and up to 51 modules with CPUs 350 through 364.
Q: How do update rates and filter frequencies differ between wiring configurations?
A: Single-ended mode provides an update rate of 6 ms per channel with a 41 Hz filter response, whereas differential mode yields a 3 ms per channel update rate with an 82 Hz filter response.