Configured for analog voltage signal processing in Series 90-30 platforms, the GE Fanuc IC693ALG222 (IC693ALG222 Analog Input Module) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model IC693ALG222
Brand GE Fanuc Emerson
Origin USA
Weight 0.88 lbs (0.40 kg)
Dimensions Single-slot Series 90-30 module width
Operating Temp 0 to 60 deg C
Power Consumption 112 mA from +5 VDC backplane bus; 41 mA from isolated +24 VDC supply
Input Channel Count 16 single-ended or 8 differential channels
Signal Voltage Ranges 0 to 10 VDC (unipolar), -10 to +10 VDC (bipolar)
Resolution (0 to +10 VDC) 2.5 mV per count (1 LSB = 2.5 mV)
Resolution (-10 to +10 VDC) 5.0 mV per count (1 LSB = 5.0 mV)
Linearity Less than 1 LSB
Absolute Accuracy +/-0.25% of full scale at 25 deg C; +/-0.5% over full operating temp
Update Rate 6 ms per channel (single-ended); 3 ms per channel (differential); 13 ms total scan
Input Filter Response 41 Hz (single-ended mode); 82 Hz (differential mode)
Isolation Voltage 1500 V RMS field to logic side
Status Indicators 2 green LEDs ("Module OK" and "Power Supply OK")

Backplane Bus Communication Velocity & I/O Density Scaling

The IC693ALG222 updates digitized 12-bit voltage representations directly to the CPU logic memory table via the backplane bus. Designed to optimize backplane bus communication velocity and I/O density scaling, it converts unipolar (0 to 10 VDC) or bipolar (-10 to +10 VDC) analog inputs across up to 16 channels in a single rack slot. Firmware flash compatibility supports automated rack scanning with channel update times down to 3 ms in differential mode and 6 ms in single-ended mode. The field-to-logic interface maintains 1500 V RMS isolation to prevent noise propagation across the backplane.

Frequently Asked Questions

Q: What are the backplane current draw requirements for the IC693ALG222?

A: The module draws 112 mA from the +5 VDC backplane bus for internal logic and 41 mA from the isolated +24 VDC backplane supply to power onboard field-side converters.

Q: What system CPU limits exist for installing multiple IC693ALG222 modules?

A: A maximum of 4 modules can be installed with CPUs 311, 313, or 323; 8 modules with CPU331 or CPU351; 12 modules with CPUs 340/341; and up to 51 modules with CPUs 350 through 364.

Q: How do update rates and filter frequencies differ between wiring configurations?

A: Single-ended mode provides an update rate of 6 ms per channel with a 41 Hz filter response, whereas differential mode yields a 3 ms per channel update rate with an 82 Hz filter response.

Field Installation Guidelines

  1. Remove primary system power from the Series 90-30 baseplate before inserting or removing the module.
  2. Align the module chassis with any open I/O slot in a 5-slot or 10-slot baseplate and push until the rear edge connector firmly seats into the backplane bus.
  3. Tighten the top panel retention screw to secure frame grounding and mechanically lock the module in place.
  4. Wire field input sources to the removable terminal block according to either the 16-channel single-ended or 8-channel differential wiring diagrams.
  5. Route low-voltage analog signal cables in grounded metal conduits separate from AC power circuits, connecting overall cable shields at a single chassis ground point.