Configured for discrete signal processing and relay load actuation in Series 90-30 platforms, the GE Fanuc IC693MDR390 (IC693MDR390 Combination Discrete Input/Output Module) provides direct physical/electrical execution.
| Parameter | Specification |
|---|---|
| Model | IC693MDR390 |
| Brand | GE Fanuc Emerson |
| Origin | USA |
| Weight | 0.69 lbs (0.31 kg) |
| Dimensions | Single-slot Series 90-30 module width |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 80 mA backplane current draw (all I/O active); 70 mA (all outputs energized) |
| Input Channels | 8 discrete DC inputs |
| Input Rated Voltage | 24 VDC nominal (-30 to +32 VDC range) |
| Input On-State Limits | 15 to 32 VDC; 4 mA minimum current |
| Input Off-State Limits | 0 to 5 VDC; 1.5 mA maximum leakage current |
| Input Current | 7.5 mA typical at rated voltage |
| Input Response Time | 7 ms typical (On and Off transitions) |
| Output Channels | 8 Normally Open (N.O.) relay contact outputs |
| Output Operating Voltage | 5 to 30 VDC; 5 to 250 VAC (50/60 Hz) |
| Output Current Rating | 2 A maximum per point; 4 A maximum per common |
| Output Response Time | 15 ms maximum (On and Off transitions) |
| Galvanic Isolation | 1500 V RMS between logic/inputs and outputs; 500 V RMS between output groups |
| Channel Diagnostics | Individual status LED indicators per I/O circuit |
The IC693MDR390 module updates 8 discrete input states and 8 relay output channels across the backplane bus to optimize backplane bus communication velocity and I/O density scaling within a single slot footprint. The input section processes 24 VDC signals with a 7 ms transition delay, while the output section features two isolated groups of four Normally Open relay contacts capable of switching up to 2 A per point across 5-30 VDC or 5-250 VAC line ranges. Internal firmware flash compatibility ensures seamless address mapping across baseplate configurations. High-density isolation rated at 1500 V RMS protects internal backplane logic from external load transients.
Q: What are the electrical rating limits for the output relay contacts?
A: Each Normally Open relay output channel supports up to 2 A maximum at operating voltages of 5 to 30 VDC or 5 to 250 VAC (50/60 Hz), with a limit of 4 A maximum per common grouping.
Q: How are the output channels grouped and isolated from one another?
A: The 8 relay output contacts are arranged into two independent groups of 4 channels each, featuring 500 V RMS galvanic isolation between groups and 1500 V RMS isolation from field logic.
Q: What is the backplane current draw for the IC693MDR390 during full operation?
A: The module draws 80 mA from the backplane bus when all input and output channels are active, and 70 mA when only the output relays are energized.
Nuestra línea de producción se paró debido a un monitor Bently Nevada defectuoso. Lo encontramos en stock aquí y lo enviaron por DHL de inmediato. Volvió a funcionar en 48 horas, lo que realmente salvó nuestra planta.
Encontrar módulos nuevos y originales es fundamental para nuestra seguridad. Este equipo entrega componentes de fábrica con certificación completa. Su compromiso de vender únicamente productos nuevos los convierte en nuestro socio de mayor confianza.
Llevamos dos años abasteciendo aquí piezas de Honeywell y Schneider. Todos nuestros envíos llegan perfectamente embalados, con los precintos originales de fábrica intactos. Ofrecemos una comunicación clara y los mejores plazos de entrega del sector.