Configured for PROFINET network node interfacing in PACSystems RX3i platforms, the GE Fanuc IC695CEP001 (IC695CEP001 Compact Expansion Carrier) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model IC695CEP001
Brand GE Fanuc Emerson
Origin United States
Weight 1.38 lbs (0.62 kg)
Dimensions 177.2 x 51 x 35 mm (7 x 2 x 1.3 in)
Operating Temp 0 to 60 deg C (32 to 140 deg F)
Power Consumption 5.25 W (0.22 A) at 24 VDC nominal (Input Range: 19.2 to 30 VDC)
Network Interface Dual RJ-45 copper 10/100 Base-TX Ethernet ports
PROFINET Version PROFINET Version 2.3 (Class A)
USB Interface 1 Micro-B USB 2.0 compliant port
I/O Capacity per Station 1 I/O module per station; 1024 bytes total I/O (512 bytes input / 512 bytes output)
Control/Status Bits 32 input status bits / 32 output control bits
Programming Software Proficy Machine Edition 8.0 SIM 5 or later

Profinet Deterministic Networks and Firmware Flash Compatibility

The IC695CEP001 integrates into Profinet deterministic networks to manage high-speed remote node scanning across ring, star, and line topologies. Featuring a built-in Micro-B USB 2.0 port, the carrier maintains complete firmware flash compatibility for local operating system upgrades without removing the module from field wiring. Dual RJ-45 copper Ethernet ports support 10/100 Mbps auto-sensing data routing, ensuring deterministic packet transport, I/O density scaling, and real-time synchronization between the central CPU and attached I/O drop hardware.

Frequently Asked Questions

Q: What software version is required to configure the IC695CEP001 carrier module?

A: The IC695CEP001 requires Proficy Machine Edition version 8.0 SIM 5 or later for system configuration, parameterization, and network setup.

Q: How many I/O modules can be mounted to a single IC695CEP001 CEP carrier station?

A: Each IC695CEP001 carrier station supports exactly 1 RX3i I/O module, handling up to 512 bytes of input data and 512 bytes of output data.

Q: What is the purpose of the onboard Micro-B USB port on the IC695CEP001?

A: The USB 2.0 Micro-B connector is dedicated to performing local maintenance tasks and updating module firmware.

Field Installation Guidelines

  1. Disconnect main line power supplying the 24 VDC field power bus before mounting or wiring the IC695CEP001 carrier.
  2. Secure the IC695CEP001 carrier to the mounting surface or DIN rail according to standard panel mechanical practices.
  3. Connect 24 VDC power conductors (19.2 to 30 VDC operating range) to the module power input terminals, maintaining correct wire polarity.
  4. Plug CAT5e or CAT6 industrial shielded Ethernet cables into the RJ-45 receptacles, verifying that cable drain wires are grounded to suppress noise.
  5. Install the designated RX3i I/O module into the carrier slot, applying power and confirming LED diagnostic indicators for active network status.