The GE Fanuc IC200ALG265, also cataloged as the IC200ALG265 Analog Input Module, operates as a dedicated hardware component for multi-channel voltage and current signal acquisition within VersaMax I/O platforms. The module processes 15 single-ended channels arranged in a single group, converting -10 to 10 VDC or 4 to 20 mA analog inputs into 15-bit digital values with integrated overvoltage protection and diagnostic detection.
| Parameter | Specification |
|---|---|
| Model | IC200ALG265 |
| Brand | GE Fanuc |
| Origin | USA |
| Weight | 3.00 lbs (1.36 kg) |
| Dimensions | Single-slot VersaMax module footprint |
| Operating Temp | 0 deg C to 60 deg C |
| Power Consumption | 100 mA maximum at 5 VDC (supplied via backplane) |
| Input Channels | 15 single-ended channels (1 group) |
| Resolution | 15-bit |
| Input Voltage Range | -10 VDC to 10 VDC |
| Input Current Range | 4 to 20 mA (1 to 20 mA functional operating limits) |
| Input Impedance | 100k Ohms |
| Update Rate | 7.5 ms |
| Measurement Accuracy | 0.3% typical, 1% maximum (derate by +/-2% under RF interference) |
| Isolation | 250 VAC continuous, 1500 VAC for 1 minute (frame to ground) |
| Status Indicator | OK LED |
The module executes direct serial communication over the VersaMax local backplane, drawing 100 mA maximum from the internal 5 VDC logic bus to transfer updated 15-bit conversion data every 7.5 ms. Built-in input protection prevents thermal and electrical damage to input sense resistors during voltage overload conditions on field loops. Dynamic register scaling and onboard diagnostic polling ensure fast cyclic transmission across deterministic PLC networks without requiring external field power supplies.
Q: Does the IC200ALG265 require an external power supply for channel processing?
A: No, the module operates entirely using 5 VDC power supplied directly through the VersaMax backplane bus structure.
Q: Are the 15 input channels isolated from one another?
A: No, all 15 single-ended input channels reside in a single common group without channel-to-channel isolation; isolation is provided at 250 VAC continuous between the system frame and ground.
Q: How does radiofrequency (RF) interference affect measurement accuracy?
A: Exposure to intense RF interference requires derating the overall analog channel accuracy by an additional +/-2%.
Nuestra línea de producción se paró debido a un monitor Bently Nevada defectuoso. Lo encontramos en stock aquí y lo enviaron por DHL de inmediato. Volvió a funcionar en 48 horas, lo que realmente salvó nuestra planta.
Encontrar módulos nuevos y originales es fundamental para nuestra seguridad. Este equipo entrega componentes de fábrica con certificación completa. Su compromiso de vender únicamente productos nuevos los convierte en nuestro socio de mayor confianza.
Llevamos dos años abasteciendo aquí piezas de Honeywell y Schneider. Todos nuestros envíos llegan perfectamente embalados, con los precintos originales de fábrica intactos. Ofrecemos una comunicación clara y los mejores plazos de entrega del sector.