100 % original. Más de 100 000 piezas en stock. Listas para enviar.

  • es

Configured for discrete AC signal processing in VersaMax control systems, the GE Fanuc IC200MDL240 (IC200MDL240 Discrete Input Module) provides direct physical/electrical execution. The unit accepts 16 discrete input channels operating at 120 VAC nominal voltage, converting field binary signals into 16-bit discrete data format across the backplane bus.

Hardware Specifications

Parameter Specification
Model IC200MDL240
Brand GE Fanuc
Origin USA
Weight 0.38 lbs (0.17 kg)
Dimensions 110 mm x 66.8 mm x 50.0 mm
Operating Temp 0 deg C to 60 deg C
Power Consumption 110 mA maximum backplane current at 5 VDC
Channel Count 16 discrete input points (2 groups of 8 channels)
Input Voltage Range 0-132 VAC (47-63 Hz), 120 VAC nominal
ON-State Range 70-132 VAC (7 mA minimum current)
OFF-State Range 0-40 VAC (1.5 mA maximum current)
Input Impedance 8.6 kOhms at 60 Hz
Response Time ON: 1 cycle; OFF: 2 ms minimum
External Power None required (logic powered from backplane)
Isolation Rating Group-to-group: 250 VAC continuous (1500 VAC for 1 min); Optical/Frame: 1500 VAC
Status Display 16 individual channel LEDs and 1 backplane status LED

Backplane Bus Communication Velocity & Firmware Flash Compatibility

The module executes binary signal evaluation across two groups of 8 channels, interfacing directly with VersaMax CPUs or Network Interface Units (NIUs). Backplane communication velocity relies on a maximum current draw of 110 mA from the 5 VDC bus, eliminating the requirement for external field power to energize internal logic circuits. Optical isolation provides 250 VAC continuous isolation between user inputs, backplane logic, and system frame ground. Firmware flash compatibility within the host controller enables seamless I/O mapping and diagnostic status reporting via the onboard LED array.

Frequently Asked Questions

Q: Does the IC200MDL240 require an external power supply to operate field inputs?

A: No external power supply is required; internal module logic draws all operational power directly from the backplane (110 mA maximum at 5 VDC).

Q: What isolation level is provided between the individual input channels?

A: The module features group-to-group optical isolation rated at 250 VAC continuous (1500 VAC for 1 minute) between its two 8-channel groups.

Q: Does vertical DIN-rail mounting impact module performance?

A: The module supports both horizontal and vertical mounting orientations without performance derating, though input voltage thermal deratings apply at 132 VAC.

Field Installation Guidelines

  1. Snap the carrier base onto a standard 35 mm DIN rail in either a horizontal or vertical orientation.
  2. Insert the IC200MDL240 module firmly into the VersaMax I/O carrier until the locking mechanisms engage.
  3. Wire incoming 120 VAC field inputs to the designated group terminals, maintaining neutral common wiring per 8-channel group.
  4. Verify that signal wiring is separated from high-voltage DC or noisy inductive lines to prevent signal distortion.
  5. Power up the system backplane and confirm that the backplane LED illuminates green to signal proper communication.