Configured for discrete AC signal processing in VersaMax control systems, the GE Fanuc IC200MDL240 (IC200MDL240 Discrete Input Module) provides direct physical/electrical execution. The unit accepts 16 discrete input channels operating at 120 VAC nominal voltage, converting field binary signals into 16-bit discrete data format across the backplane bus.
| Parameter | Specification |
|---|---|
| Model | IC200MDL240 |
| Brand | GE Fanuc |
| Origin | USA |
| Weight | 0.38 lbs (0.17 kg) |
| Dimensions | 110 mm x 66.8 mm x 50.0 mm |
| Operating Temp | 0 deg C to 60 deg C |
| Power Consumption | 110 mA maximum backplane current at 5 VDC |
| Channel Count | 16 discrete input points (2 groups of 8 channels) |
| Input Voltage Range | 0-132 VAC (47-63 Hz), 120 VAC nominal |
| ON-State Range | 70-132 VAC (7 mA minimum current) |
| OFF-State Range | 0-40 VAC (1.5 mA maximum current) |
| Input Impedance | 8.6 kOhms at 60 Hz |
| Response Time | ON: 1 cycle; OFF: 2 ms minimum |
| External Power | None required (logic powered from backplane) |
| Isolation Rating | Group-to-group: 250 VAC continuous (1500 VAC for 1 min); Optical/Frame: 1500 VAC |
| Status Display | 16 individual channel LEDs and 1 backplane status LED |
The module executes binary signal evaluation across two groups of 8 channels, interfacing directly with VersaMax CPUs or Network Interface Units (NIUs). Backplane communication velocity relies on a maximum current draw of 110 mA from the 5 VDC bus, eliminating the requirement for external field power to energize internal logic circuits. Optical isolation provides 250 VAC continuous isolation between user inputs, backplane logic, and system frame ground. Firmware flash compatibility within the host controller enables seamless I/O mapping and diagnostic status reporting via the onboard LED array.
Q: Does the IC200MDL240 require an external power supply to operate field inputs?
A: No external power supply is required; internal module logic draws all operational power directly from the backplane (110 mA maximum at 5 VDC).
Q: What isolation level is provided between the individual input channels?
A: The module features group-to-group optical isolation rated at 250 VAC continuous (1500 VAC for 1 minute) between its two 8-channel groups.
Q: Does vertical DIN-rail mounting impact module performance?
A: The module supports both horizontal and vertical mounting orientations without performance derating, though input voltage thermal deratings apply at 132 VAC.
Nuestra línea de producción se paró debido a un monitor Bently Nevada defectuoso. Lo encontramos en stock aquí y lo enviaron por DHL de inmediato. Volvió a funcionar en 48 horas, lo que realmente salvó nuestra planta.
Encontrar módulos nuevos y originales es fundamental para nuestra seguridad. Este equipo entrega componentes de fábrica con certificación completa. Su compromiso de vender únicamente productos nuevos los convierte en nuestro socio de mayor confianza.
Llevamos dos años abasteciendo aquí piezas de Honeywell y Schneider. Todos nuestros envíos llegan perfectamente embalados, con los precintos originales de fábrica intactos. Ofrecemos una comunicación clara y los mejores plazos de entrega del sector.