Configured for field contact status sensing and discrete signal acquisition in Series 90-30 platforms, the GE Fanuc IC693MDL241 (IC693MDL241 Discrete Input Module) provides direct physical/electrical execution.
| Parameter | Specification |
|---|---|
| Model | IC693MDL241 |
| Brand | GE Fanuc Emerson |
| Origin | USA |
| Weight | 0.69 lbs (0.31 kg) |
| Dimensions | Single-slot Series 90-30 module width |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 80 mA at 5 VDC (all inputs active); 125 mA from isolated 24 VDC backplane bus or external user supply |
| Number of Channels | 16 discrete input channels (single group of 16 inputs) |
| Nominal Input Voltage | 24 VAC / 24 VDC |
| Input Voltage Range | 0 to +30 VDC or 0 to +30 VAC (50/60 Hz) |
| Wiring Configuration | Positive / Negative logic (sink / source) |
| On-State Voltage | 11.5 to 30.0 VAC / VDC |
| Off-State Voltage | 0 to 4 VAC / VDC |
| On-State Current | 3.2 mA minimum |
| Off-State Current | 1 mA maximum |
| Input Current | 7 mA at rated voltage |
| Response Times | On response: 12 ms maximum; Off response: 28 ms maximum |
| Galvanic Isolation | 1500 V RMS (1500 VAC) between field side and logic side |
| Logic Reading | %I memory table |
| LED Indicators | 16 green status LEDs (2 rows of 8: A1-A8, B1-B8) |
The IC693MDL241 input module updates discrete channel data into the CPU %I logic memory map across the backplane bus within a 12 ms On-response and 28 ms Off-response delay. Optimized for backplane bus communication velocity and I/O density scaling, the 16-point single-group topology supports positive or negative logic in DC mode, as well as 50/60 Hz AC signals. Logic-side circuits draw 80 mA from the 5 VDC backplane bus when all channels are active, while field power consumes 125 mA from the isolated 24 VDC bus or a user-provided power supply. Galvanic isolation of 1500 V RMS protects the internal backplane logic from external field circuit spikes.
Q: What power sources can be used to supply the input field circuits on the IC693MDL241?
A: Field circuits can be powered using an external 24 VAC/VDC user supply or the isolated 24 VDC output supplied directly by the baseplate power supply.
Q: What are the logic threshold limits for detecting On and Off channel states?
A: The module registers an On-state at 11.5 to 30.0 VAC/VDC (3.2 mA minimum) and an Off-state at 0 to 4 VAC/VDC (1 mA maximum off-state current).
Q: What are the backplane current draw requirements for this 16-point input module?
A: The module consumes 80 mA from the 5 VDC backplane bus when all 16 inputs are ON, plus 125 mA from the isolated 24 VDC backplane supply or external user source.
Nuestra línea de producción se paró debido a un monitor Bently Nevada defectuoso. Lo encontramos en stock aquí y lo enviaron por DHL de inmediato. Volvió a funcionar en 48 horas, lo que realmente salvó nuestra planta.
Encontrar módulos nuevos y originales es fundamental para nuestra seguridad. Este equipo entrega componentes de fábrica con certificación completa. Su compromiso de vender únicamente productos nuevos los convierte en nuestro socio de mayor confianza.
Llevamos dos años abasteciendo aquí piezas de Honeywell y Schneider. Todos nuestros envíos llegan perfectamente embalados, con los precintos originales de fábrica intactos. Ofrecemos una comunicación clara y los mejores plazos de entrega del sector.