The Emerson KJ4001X1-BA2 (also identified as VE3051CO or 12P1562X012) is a 2-wide power controller carrier engineered for the DeltaV M-Series distributed control system. This module serves as a fundamental physical and electrical interface, providing secure mounting and stable power distribution for controllers and power supply units across the LocalBus. Designed for demanding industrial environments, it ensures the reliability of the control network in sectors such as power generation, chemical processing, and large-scale manufacturing.

Features

  • Designed specifically for the DeltaV M-Series architecture.
  • 2-wide carrier configuration for efficient cabinet space utilization.
  • Facilitates reliable power distribution and LocalBus communication.
  • Rated for operation in hazardous area environments (II 3 G).
  • Supports robust mechanical mounting for high-vibration industrial settings.

Applications

This carrier is intended for use in DeltaV control cabinets where high-availability power management is required. It is suitable for applications involving continuous process control, safety-critical instrumentation, and complex automation systems where system uptime and signal integrity are paramount.

Technical Specifications

Model KJ4001X1-BA2 (12P1562X012)
Brand Emerson
Series DeltaV M-Series
Input Rating 30 VDC, 8 A Max
Operating Temperature 0 to 60 deg C
Humidity 5 to 95 percent (non-condensing)
Hazardous Rating II 3 G / EEx nA IIC T4
Certification Nemko 02ATEX431U
Contaminant Rating ISA-S71.04-1985 Class G3
Vibration Resistance 1 mm P-P (5-16 Hz); 0.5g (16-150 Hz)
Max Bus Length 6.5 meters

Installation Guidelines

  • Ensure the system is fully de-energized before installing or removing the carrier or any associated LocalBus cables.
  • Use KJ4001X1-FA1 module covers on all unused slots to prevent dust and debris ingress.
  • Verify that the total length of the LocalBus, including all I/O carriers and extenders, does not exceed 6.5 meters to maintain signal timing.
  • Mount in a clean, ventilated enclosure to maintain the specified IP20 protection and operating temperature range.
  • Handle with standard ESD precautions to prevent damage to sensitive electronic components.

FAQ

What is the primary function of the KJ4001X1-BA2?
This module acts as a base carrier for DeltaV controllers, providing the necessary mechanical support and electrical power interface to the LocalBus.

Can this module be used in hazardous locations?
Yes, it is rated for use in hazardous areas under II 3 G / EEx nA IIC T4 standards, provided it is installed according to the relevant ATEX guidelines.

Is there a limit to the bus length when using this carrier?
Yes, the total combined length of all I/O carriers and LocalBus extenders in a single chain must not exceed 6.5 meters.