أصلي 100%. أكثر من 100,000 قطعة متوفرة. جاهزة للشحن.

  • ar

The GE Fanuc IC693PWR331, also cataloged as the IC693PWR331 High-Capacity Power Supply Module, operates as a dedicated hardware component for internal backplane bus powering and DC voltage conversion within Series 90-30 PLC systems.

Hardware Specifications

Parameter Specification
Model IC693PWR331
Brand GE Fanuc Emerson
Origin USA
Weight 1.25 lbs (0.57 kg)
Dimensions Single-slot Series 90-30 module width
Operating Temp 0 to 60 deg C
Power Consumption 50 W with VDC Input / 90 VA with VAC Input
Nominal Rated Voltage 24 VDC / 48 VDC
Input Voltage Range Start: 21 to 56 VDC / Run: 18 to 56 VDC
Inrush Current 4 A peak, 100 ms maximum
Output Capacity Total 30 Watts maximum load capacity
Output Voltages +5 VDC (30 W max), +24 VDC Relay (15 W max), +24 VDC Isolated (20 W max)
Holdup Time 14 ms minimum
Physical Terminals 3 terminal screws
Diagnostic Display PWR, OK, RUN, BATT LED indicators

Backplane Bus Communication Velocity & Firmware Power Distribution

The IC693PWR331 power supply module converts primary DC input power to distribute +5 VDC logic power alongside auxiliary +24 VDC relay and isolated +24 VDC output rails directly to the Series 90-30 backplane. Deterministic network timing and backplane bus communication velocity rely on low ripple regulation across the 5 VDC rail during module processing cycles. Internal firmware execution and CPU logic hold-up functions are sustained through a minimum 14 ms holdup time during brief primary DC input voltage dropouts. Primary input power conditioning suppresses inrush current spikes to a maximum of 4 A peak for 100 ms during initial rack power-up sequence.

Frequently Asked Questions

Q: What are the primary output voltage rails supplied by the IC693PWR331 module to the backplane?

A: The module provides three distinct output voltage rails: +5 VDC (up to 30 Watts), +24 VDC Relay (up to 15 Watts), and +24 VDC Isolated power (up to 20 Watts), with total combined load capacity not exceeding 30 Watts.

Q: What is the required DC input operating voltage range for starting and running the unit?

A: The module requires a starting input range of 21 to 56 VDC and maintains continuous operation across a running input range of 18 to 56 VDC.

Q: How does the IC693PWR331 report system power status to the user?

A: Hardware operational status and backplane health are monitored on the front panel via four diagnostic LED indicators: PWR, OK, RUN, and BATT.

Field Installation Guidelines

  1. Ensure incoming DC power lines are fully de-energized and locked out prior to connecting conductors to the 3 physical terminal screws.
  2. Align the module card edges with the leftmost power slot guide of the Series 90-30 rack baseplate and push firmly until the backplane connector locks in place.
  3. Secure the top retaining screw to establish structural chassis grounding and mitigate physical displacement from vibration.
  4. Connect the primary 24 VDC or 48 VDC supply wiring using proper wire gauges and maintain solid functional earth bonding to eliminate electrical noise.
  5. Maintain adequate ventilation clearance above and below the baseplate rack chassis to facilitate passive thermal convection cooling.