The GE Fanuc IC697PWR724, also cataloged as the IC697PWR724 Power Supply Module, operates as a dedicated hardware component for stable DC voltage distribution and system backplane powering within Series 90-70 VME rack systems.

Hardware Specifications

Parameter Specification
Model IC697PWR724
Brand GE Fanuc Emerson
Product Line Series 90-70
Origin USA
Weight 2.50 lbs (1.13 kg)
Dimensions Standard Series 90-70 single-slot module width
Operating Temp 0 to 60 deg C
Power Consumption 160 Watts
Nominal Rated Voltage 24 VDC
Input Voltage Range 18 to 32 VDC
Input Inrush Energy 22 J maximum
Output Power 90 Watts maximum
Output Voltage +5 VDC, +12 VDC, and -12 VDC
Overvoltage Limit 5 VDC output overvoltage protection limit
Ride-Through Time 10 ms
Backplane Compatibility VME Compatible

Backplane Bus Communication Velocity & Power Distribution

The IC697PWR724 module features dedicated internal power conversion circuitry tailored for high-density Series 90-70 backplane configurations. It delivers regulated +5 VDC logic power alongside auxiliary +12 VDC and -12 VDC rails to feed input/output circuits and processing cards across the backplane bus. System firmware flash compatibility and deterministic backplane communication velocity across the VME architecture rely on low-ripple output voltages during transient load demands. The internal power stage incorporates a controlled input inrush energy circuit rated up to 22 J to mitigate voltage sag on the primary 24 VDC feeder bus during initial system energization.

Frequently Asked Questions

Q: Can the IC697PWR724 module supply power to expansion racks in a Series 90-70 system?

A: Yes, the IC697PWR724 can provide power to a second rack in single or expansion configurations, provided the combined power drain across all connected rails does not exceed the maximum output limit of 90 Watts.

Q: What is the behavior of the supply during short primary power interruptions?

A: The module maintains a minimum ride-through time of 10 ms under full load conditions, permitting execution of hold-up functions before system power failure logic triggers.

Q: Is hot-swapping permitted for the IC697PWR724 module during backplane operation?

A: No, primary 24 VDC input power must be isolated and the backplane de-energized prior to inserting or removing the power supply module to prevent electrical arcing and backplane bus signal corruption.

Field Installation Guidelines

  1. Verify that incoming DC power wires are de-energized and tagged out prior to terminal connection. Ensure the supply line voltage remains strictly within the specified 18 to 32 VDC window.
  2. Align the module card edges with the designated rack slot guides of the Series 90-70 chassis. Slide the module firmly into place until the backplane connectors seat completely.
  3. Tighten the top and bottom retaining screws to secure the chassis ground bond and prevent physical displacement due to vibration.
  4. Wire primary 24 VDC input power using appropriate wire gauges, ensuring strict adherence to polarity and shield grounding standards to eliminate ground loops.
  5. Provide a minimum clearance of 50 mm above and below the rack chassis to ensure adequate convection airflow across thermal dissipation surfaces.