أصلي 100%. أكثر من 100,000 قطعة متوفرة. جاهزة للشحن.

  • ar

Configured for 24 VDC discrete signal acquisition in VersaMax PLC and I/O station architectures, the GE IC200MDL640 (IC200MDL640 Discrete Input Module) provides direct physical/electrical execution. The module processes field signals across 16 input points split into 2 isolated groups of 8 channels. Supporting both positive (sinking) and negative (sourcing) wiring configurations, it conditions incoming DC signals via an internal 10k Ohm impedance network and routes state data to the host CPU or Network Interface Unit (NIU) with a configurable input filter response time ranging from 0 ms to 7.0 ms.

Hardware Specifications

Parameter Specification
Model IC200MDL640
Brand General Electric
Origin USA
Weight 0.11 kg
Dimensions Standard VersaMax Single-Slot Carrier Profile
Operating Temp 0 to 60 deg C
Power Consumption 25 mA @ 5 VDC (Backplane draw)
Module ID FFFF8008
Input Channels 16 Discrete Inputs (2 isolated groups of 8)
Nominal Operating Voltage 24 VDC (0 to 30 VDC maximum range)
On-State Voltage 15 to 30 VDC
Off-State Voltage 0 to 5 VDC
Input Impedance 10k Ohms
Response Time 0.5 ms basic ON/OFF time; Configurable filter (0 ms, 1.0 ms default, 7.0 ms max)
Isolation 250 VAC continuous group-to-group (1500 VAC for 1 min); No channel-to-channel isolation within groups
External Power Requirement None
Status Display 16 point LEDs, 1 backplane "OK" LED

Profinet / EtherNet/IP Deterministic Networks & Backplane Attributes

The IC200MDL640 maintains high backplane bus communication velocity when executing cyclic I/O scans across VersaMax carrier networks. Drawing a maximum of 25 mA from the 5 VDC logic bus, the module optimizes rack-level power allocation without requiring external field power supplies. Configurable input filter settings suppress industrial contact bounce, preserving deterministic scan timing over Profinet or EtherNet/IP network drops. High I/O density scaling is achieved through snap-in carrier bases, while native hardware ID flags ensure complete firmware flash compatibility and hot-swap validation during live module exchanges.

Frequently Asked Questions

Q: Does the IC200MDL640 require an auxiliary 24 VDC external power supply connection to power internal module logic?

A: No. The internal logic and operational circuits draw all necessary power directly from the 5 VDC backplane bus at a maximum current consumption of 25 mA.

Q: Can channels on the IC200MDL640 be wired in both sinking and sourcing field device configurations?

A: Yes. The 16 input channels accommodate both positive logic (sinking current from the field device) and negative logic (sourcing current to the field device) depending on how the field device is referenced to the group common terminal.

Q: Is hot-swapping supported for the IC200MDL640 module?

A: Yes. The module supports live insertion and removal on its VersaMax carrier base; however, proper alignment and steady mechanical handling are required during insertion to prevent backplane bus communication disruption to adjacent I/O modules.

Field Installation Guidelines

  1. Power Safety: Shut off main cabinet power prior to mounting, removing, or wiring carrier bases to prevent shock hazards and transient arcs.

  2. Carrier Base Snap-In: Position the IC200MDL640 module over the target VersaMax carrier slot. Press down firmly until the locking tabs snap into place, ensuring complete seating against the backplane connector.

  3. Field Wiring Connections: Connect field inputs to the terminal strip on the carrier base. Connect signal wires between the input terminal and group common. When additional bussing is required, install a shorting bar on the designated carrier terminal strip.

  4. Noise Isolation & Shielding: Separate 24 VDC discrete signal wiring from high-voltage AC power lines and drive output cables within terminal raceways to maintain 10k Ohm input signal integrity.

  5. Grounding Verification: Ensure the carrier DIN rail or panel surface is connected to protective earth (PE) to validate the 250 VAC group-to-group isolation rating.