أصلي 100%. أكثر من 100,000 قطعة متوفرة. جاهزة للشحن.

  • ar

The GE IC693MDL340, also cataloged as the IC693MDL340 Discrete Output Module, operates as a dedicated hardware component for 120 VAC load actuation within Series 90-30 PLC platforms.

Hardware Specifications

Parameter Specification
Model IC693MDL340
Brand GE Fanuc / Emerson Automation
Origin USA
Weight 0.45 kg (1.00 lbs)
Dimensions Single-slot Series 90-30 module format
Operating Temp 0 to 60 deg C
Power Consumption 315 mA from internal +5 VDC bus (all outputs ON)
Output Points 16 points
Output Grouping 2 isolated groups (8 channels per group with 1 common)
Rated Output Voltage 120 VAC nominal (85 to 132 VAC range, 50/60 Hz)
Output Current per Point 0.5 A maximum
Output Current per Group 3.0 A maximum
Minimum Load Current 50 mA
Maximum Inrush Current 20 A for one cycle
Output Response Time ON delay: 1 ms max; OFF delay: 1/2 cycle max
Voltage Drop / Leakage 1.5 VAC max drop; 2 mA max leakage at 120 VAC
Isolation Rating 1500 V field-to-logic; 500 V group-to-group

Backplane Bus Communication Velocity & Network Execution

The module processes discrete logic execution commands received over the backplane bus to control connected field actuators. System-level backplane bus communication velocity guarantees deterministic scan updating, while onboard LED diagnostics provide per-channel status feedback and blown-fuse indication for physical loop verification.

Frequently Asked Questions

Q: What is the backplane current draw for the IC693MDL340 module? A: The module consumes 315 mA from the +5 VDC backplane supply when all 16 output channels are in the ON state.

Q: What are the output current limitations per point and per group? A: Each individual output channel handles up to 0.5 A, while each 8-channel group supports a maximum continuous current load of 3.0 A.

Q: How is galvanic isolation structured across the output circuits? A: The module provides 1500 V isolation between field-side circuits and logic-side backplane electronics, and 500 V isolation between the two independent output groups.

Field Installation Guidelines

  • Baseplate Slot Insertion: De-energize backplane power prior to inserting or removing the module from the Series 90-30 baseplate to protect edge connector contacts.
  • AC Output Line Wiring: Wire 120 VAC field power to the group commons on the terminal block. Ensure total current per group does not exceed 3.0 A continuous load.
  • Inductive Load Suppression: Install metal oxide varistors (MOVs) or RC snubbers across inductive AC field devices (such as solenoid valves and relay coils) to suppress voltage transients during switching.
  • Shield & Earth Grounding: Secure all field cable shielding and baseplate mounting brackets directly to the enclosure master ground bus to mitigate electromagnetic noise coupling.