The GE IC694MDL732, also cataloged as the IC694MDL732 Discrete Output Module, operates as a dedicated hardware component for field load driving within RX3i PACSystem platforms. The module sources DC power to field control loads through 8 discrete output points, converting controller backplane signals into 12-24 VDC output operations.
| Parameter | Specification |
|---|---|
| Model | IC694MDL732 |
| Brand | GE Fanuc Emerson |
| Series | RX3i PACSystem |
| Product Type | Discrete Output Modules |
| Output Points | 8 points (1 group) |
| Output Logic | Positive logic (sourcing) |
| Rated Voltage | 12-24 VDC |
| Output Voltage Range | 12-24 VDC |
| Output Current | 0.5 A per point (2.0 A maximum per common) |
| Inrush Current | 4.78 A for 10 ms |
| Response Time | 2 ms maximum (On/Off) |
| Power Consumption | 50 mA from backplane |
| Isolation | 250 VAC continuous, 1500 VAC for 1 min |
| Status Indicators | 8 LEDs (output state display) |
| Protection | None (no internal fuses) |
| Operating Temp | 0 to 60 deg C |
| Dimensions | Single-slot RX3i module footprint |
| Weight | 1.36 kg (3.00 lbs) |
| Origin | USA |
The IC694MDL732 interfaces with the RX3i universal backplane bus to execute state updates dispatched from the CPU. High backplane bus communication velocity maintains deterministic cycle execution across all output points. Onboard firmware flash compatibility facilitates integration into existing rack configurations, enabling synchronized signal updates without interrupting adjacent system I/O routines.
Q: Does the IC694MDL732 support hot-swapping during chassis operation?
A: Yes, the module supports hot-swap functionality, allowing physical insertion or removal from the RX3i backplane rack without interrupting system backplane power.
Q: Are there internal protective fuses built into the IC694MDL732 output channels?
A: No, the module contains no internal fuses or circuit breakers. External fuse protection must be provided on the field wiring lines.
Q: What is the maximum current rating per output point and per common group?
A: Each individual output point supports a continuous current rating of 0.5 A, with a maximum limit of 2.0 A across the shared common connection.