أصلي 100%. أكثر من 100,000 قطعة متوفرة. جاهزة للشحن.

  • ar

Yokogawa ATK4A-00 CENTUM VP KS Cable Interface Adapter

The Yokogawa ATK4A-00, also cataloged as the ATK4A KS Cable Interface Adapter, operates as a dedicated hardware component for high-density signal termination and cable interface conversion within Yokogawa CENTUM VP and CS 3000 DCS platforms. Mounting directly onto compatible analog I/O modules (such as AAI143, AAI135, AAI835, and AAP135 series), the unit converts internal module connectors into standardized KS multi-core cable interfaces for direct connection to AEA4D or AET4D terminal boards. This physical coupling eliminates point-to-point manual cabinet wiring while preserving channel assignment for 8-point and 16-point analog configurations.

Suffix Breakdown & Model Matrix

Suffix Code Specification Functional Description
ATK4A Base Model KS Cable Interface Adapter for Analog I/O Modules
-00 Standard Option Standard configuration for KS1/KS2 cable termination

Hardware Specifications

Parameter Specification
Model ATK4A-00
Brand Yokogawa
Origin Japan
Weight 0.20 kg net (1.20 kg shipping package)
Dimensions 30 mm W x 100 mm H x 130 mm D
Operating Temp 0 to +55 deg C
Power Consumption Passive pass-through adapter (no internal power draw)
Connecting Points 8-point or 16-point analog interface channels
Cable Compatibility KS1 and KS2 multi-core interface cables
Module Compatibility AAI143, AAI135, AAI835, AAP135 series
Terminal Board Compatibility AEA4D, AET4D, and KS series terminal units
Ingress Protection IP54 enclosure protection rating

4-20 mA HART Loop Protocol & Channel-to-Channel Isolation Integration

The ATK4A-00 adapter transfers 4-20 mA HART loop protocol carrier frequencies and high-frequency pulse inputs from field transmitters through dedicated multi-pin KS connectors without signal degradation. Internal pin traces maintain low loop resistance and high dielectric separation between adjacent channel lines, relying on the host I/O module and terminal boards for channel-to-channel isolation and galvanic protection. The unit incorporates grounding shield planes that route cable screen drains directly to functional chassis ground, suppressing external EMI and common-mode voltage noise across sensitive process loops.

Frequently Asked Questions

Q: Does the ATK4A-00 cable interface adapter require independent DC auxiliary power connections?

A: No. The adapter operates strictly as a passive electrical interface and pass-through termination assembly, drawing no current from the backplane or external field supplies.

Q: Can the ATK4A-00 adapter be attached or detached while the host analog I/O module remains powered?

A: Hot-plugging the adapter is not recommended during active process operations. Field loops should be de-energized or switched to manual control prior to mating or unseating multi-core KS cable assemblies to prevent transient open-circuit trips.

Q: What prevents wiring inversion or incorrect pin alignment during KS cable insertion?

A: The integrated KS cable connector housing features keyed physical guide slots that enforce correct alignment and prevent inverted cable mating.

Field Installation Guidelines

  • Direct Module Mounting: Align the ATK4A-00 rear pins precisely with the front terminal connector of the host analog module, pushing evenly until the locking latches snap into place.
  • KS Cable Engagement: Insert the KS1/KS2 multi-core cable plug straight into the adapter socket, tightening the side retaining screws to secure the connector against vibration.
  • Shield Continuity: Ensure the KS cable overall shield braid bonds securely to the grounding lug on the terminal board or cabinet earth bus bar to preserve noise immunity across analog channels.
  • Cable Strain Relief: Anchor all heavy multi-core KS field cables to cabinet wiring tie bars within 100 mm of the module faceplate to relieve mechanical tension on the ATK4A-00 connector body.