The Yokogawa SDV144-S13/D4A00 S2, also cataloged as the SDV144 Digital Input Module, operates as a dedicated hardware component for contact signal acquisition within ProSafe-RS and CENTUM VP systems. It processes no-voltage contact signals from switches, relays, and sensors across 16 channels, converting physical contact states into logical data. Configured with ISA Standard G3 conformal coating and the D4A00 cable interface, the module provides direct electrical signal isolation and system bus communication.
| Parameter | Specification |
|---|---|
| Model | SDV144-S13/D4A00 S2 |
| Brand | Yokogawa |
| Origin | Japan |
| Weight | 0.36 - 0.41 kg (1.5 kg shipping weight) |
| Dimensions | Standard Yokogawa I/O module footprint |
| Operating Temp | -20 to 70 deg C |
| Power Consumption | 290 mA (5 VDC), 140 mA (24 VDC) |
| Number of Inputs | 16 channels |
| Input Signal Type | No-voltage contact signals (ON <= 1 kOhm, OFF >= 100 kOhm) |
| Rated Contact Voltage | 24 VDC +/- 5% |
| Rated Contact Current | >= 10 mA |
| Max Permissible Input Voltage | 30 VDC |
| Response Time | <= 40 ms |
| Isolation Voltage | 1500 VAC between input terminals and system logic for 1 minute |
Yokogawa DCS and safety architectures require isolation barriers to protect backplane processing units from field electrical anomalies. The SDV144-S13 provides 1500 VAC galvanic isolation between field input circuits and system logic channels. Combining channel isolation with optional Signal Conditioner Block (SCB) modules enables active line diagnostics for open and short circuit detection, suppressing ground loop noise and preventing field fault propagation across the I/O bus.
Q: What input conditions are required to trigger an ON or OFF state on the SDV144-S13 module? A: The module registers an ON state when field contact resistance is <= 1 kOhm and an OFF state when loop resistance rises to >= 100 kOhm.
Q: Does the SDV144-S13/D4A00 support dual-redundant operation during live system execution? A: Yes, the unit supports dual-redundant pair configurations and hot-swapping to maintain uninterrupted process execution during maintenance.
Q: How does the module handle environmental protection against harsh chemical atmospheres? A: The S13 suffix indicates ISA Standard G3 conformal coating protection, extending operating temperature boundaries from -20 to 70 deg C.
Nuestra línea de producción se paró debido a un monitor Bently Nevada defectuoso. Lo encontramos en stock aquí y lo enviaron por DHL de inmediato. Volvió a funcionar en 48 horas, lo que realmente salvó nuestra planta.
Encontrar módulos nuevos y originales es fundamental para nuestra seguridad. Este equipo entrega componentes de fábrica con certificación completa. Su compromiso de vender únicamente productos nuevos los convierte en nuestro socio de mayor confianza.
Llevamos dos años abasteciendo aquí piezas de Honeywell y Schneider. Todos nuestros envíos llegan perfectamente embalados, con los precintos originales de fábrica intactos. Ofrecemos una comunicación clara y los mejores plazos de entrega del sector.