Product Overview

The Allen Bradley 1756-PB72 functions as a high-performance DC-input power supply designed specifically for ControlLogix chassis. This single-slot module installs directly into the standard power supply slot on the left side of the rack, delivering regulated backplane power to drive CPUs, I/O modules, and communication cards. It sources 100% original, brand-new components to guarantee continuous uptime in demanding process control, automotive manufacturing, and utility automation facilities.

Technical Specifications

Parameter Specification
Manufacturer Allen Bradley
Product Line ControlLogix
Part Number 1756-PB72 (Series C)
Condition 100% Brand New Original
Nominal Input Voltage 24V DC
Input Voltage Range 18-32V DC (19-32V DC operational range)
Max. Input Power 95 Watts
Max. Output Power 75 Watts at 0 to 60 degrees Celsius
Backplane Current Capacity 13 A at 5V DC, 2.8 A at 24V DC, 2.8 A at +/-12V DC
Max. Inrush Current 30 Amps
Continuous Isolation Voltage 250 Volts (Between power input and backplane)
Insulation Type Reinforced Insulation
Conductor Screw Torque 0.565 Nm
Operating Temperature 0 to +60 degrees Celsius
Storage Temperature -40 to +85 degrees Celsius
Humidity 5% to 95% non-condensing
Protection Layout Overload, short-circuit, and thermal shutdown

Engineering Advantages

  • Mitigates Voltage Fluctuations: The wide input range (18-32V DC) protects the control system from heavy machinery voltage drops on the factory floor, ensuring the PLC remains online during DC grid strain.

  • Simplifies Dense Rack Thermal Management: The high-efficiency design delivers full 75W output up to 60 degrees Celsius. This prevents localized hot spots in tight, unventilated enclosures and eliminates the need for external cooling fans.

  • Eliminate Ground Loop Noise: The 250V reinforced insulation barriers separate the raw input power lines from the sensitive digital backplane. This stops electromagnetic interference (EMI) from corrupting analog I/O signals.

  • Saves Footprint Space: The compact, single-slot mounting mechanism mounts directly to the chassis edge, leaving all standard slots open for operational I/O modules.

FAQs

  • Can I use the 1756-PB72 in a system that requires AC power?

    No. This module accepts only DC input voltages (18-32V DC). Connecting this unit to AC mains will damage the internal circuitry. You must use an external AC-to-DC step-down transformer or source an AC-native ControlLogix power supply model instead.

  • Does this power supply support hot-swapping or redundancy configurations?

    No. The 1756-PB72 is a standard single-slot power supply. You must power down the chassis completely before replacing or servicing this module. For redundant architectures, choose the 1756-PR2 framework.

  • What wire sizes and installation constraints should I use for safety?

    Use solid or stranded copper wire rated for the operational temperature environment. Secure the terminal block conductor screws to a torque of exactly 0.565 Nm to prevent loose connections or arcing under heavy industrial vibration.