100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

Product Overview

The Allen Bradley 1746-IA16 acts as a high-density, discrete AC input module for the legacy SLC 500 platform. This single-slot module reads 100/120V AC status signals from field-level command equipment, including pushbuttons, limit switches, selector dials, and motor starter auxiliary contacts. It bridges the gap between field infrastructure and control processors by translating external electrical logic into digital backplane commands. We provide this component as a 100% brand-new, original unit to secure immediate deployment compatibility and extend the operating lifespans of active factory chassis.

Technical Specifications

Parameter Specification
Manufacturer Allen Bradley
Product Line SLC 500 System
Part Number 1746-IA16 (Series B Variant)
Condition 100% Brand New Original
Module Type Digital AC Input Module
Number of Inputs 16 Channels
Points per Common 16 Points Shared via 1 Common Line
Voltage Category 100/120V AC Signal Input
Operating Voltage Range 85 to 132 VAC at 47 to 63 Hz
Nominal Input Current 10 mA per channel at 120 VAC
Max. Signal Transmission Delay Turn-on: 35 ms / Turn-off: 45 ms
Typical Internal Signal Delay 8 to 10 ms typical
Galvanic Electrical Isolation 1500 V continuous channel-to-backplane
Status Display Indicators Dedicated LED per input channel
Backplane Current Draw 0.085 A (85 mA) at 5 VDC nominal
Operating Temperature 0 to +60 degrees Celsius
Storage Temperature Profile -40 to +85 degrees Celsius
Environmental Humidity Scope 5 percent to 95 percent non-condensing
Physical Weight 0.45 kg net / 2.5 kg shipping weight

Engineering Advantages

  • Suppresses High-Voltage Inductive Noise: Built-in 1500V optical isolation paths cleanly separate the volatile 120V AC field loops from the low-voltage microchips on the SLC backplane. This protects the CPU from destructive voltage anomalies caused by raw electrical surges.

  • Maximizes Density per Chassis Slot: Packing 16 independent input channels into a single operational slot layout allows system integration engineers to scale up field device capacity without purchasing secondary expansion racks or adding internal power supplies.

  • Simplifies Floor-Level Fault Finding: A matrix of 16 front-panel status LEDs maps active electricity profiles instantly. Technicians can visually trace live signals or pinpoint failed sensor lines right on the module faceplate without opening engineering software tools.

  • Lowers Total Internal Heat Loading: Pulling only 85 mA at 5V DC from the local power grid minimizes the module power footprint. This reduced draw maintains low internal ambient operating criteria, preventing adjacent communication and processing modules from experiencing early thermal wear.

FAQs

  • Can the 1746-IA16 handle 24V DC or low-voltage DC signals?

    No. This specific input card operates exclusively within an AC voltage framework (85-132 VAC). Connecting lower-voltage DC lines will not overcome the turn-on threshold of the internal optical isolators, resulting in missed signals and software diagnostic failures.

  • How are the 16 input points grouped for wiring on this terminal block?

    The 1746-IA16 features an architecture with 16 points per common line. This means all 16 AC input field circuits connect back to a single shared neutral return terminal on the block, requiring that all monitored devices derive from the same local AC distribution phase.

  • Does this module support hot-swapping while the SLC chassis is powered up?

    No. The SLC 500 system architecture does not support RIUP (Removal and Insertion Under Power). You must isolate and shut down all primary chassis power before sliding this brand-new module into position to avoid arching across backplane pin arrays.