The ICS Triplex T3420A, also cataloged as the T3420A Analog Input Module, operates as a dedicated hardware component for processing differential physical voltage and current signals within Regent control networks. The module executes signal conversions across 16 analog input channels and 16 analog output channels with a 16-bit resolution rating and a sampling frequency of 1 kHz per channel. Utilizing an onboard micro-architecture, the hardware executes real-time digital filtering and enforces a 1500 V RMS galvanic isolation barrier between field-side conditioning circuits and the central logic processing backplane.
| Parameter | Specification |
|---|---|
| Model | T3420A |
| Brand | ICS Triplex (Rockwell Automation) |
| Origin | United Kingdom |
| Weight | 0.8 kg |
| Dimensions | 12.5 cm x 10 cm x 7.5 cm |
| Operating Temp | -20 to +60 deg C |
| Power Consumption | Not specified (24 VDC external loop supply) |
| Input Channels | 16 Channels |
| Output Channels | 16 Channels |
| Input Signal Range | 0-20 mA, 4-20 mA, 0-10 V, 1-5 V |
| Output Signal Range | 0-20 mA, 4-20 mA, 0-10 V |
| Resolution | 16-bit |
| Accuracy | +/-0.1 percent of full scale |
| Sampling Rate | 1 kHz per channel |
| Isolation | 1500 V RMS |
The T3420A interface links field instrumentation directly to a triple modular redundancy (TMR) 2oo3 architecture logic platform. Internal signal pathways utilize galvanic isolation rated at 1500 V RMS to prevent common-mode voltage spikes from disrupting the voted processor backplane. When an input loop out-of-range state or internal analog-to-digital converter mismatch is detected, the module immediately commands a fail-safe state execution, driving the affected channel values to a pre-configured safe low or high state to maintain predictable process interlocks.
Q: How does the T3420A module handle mixed voltage and current signals simultaneously?
A: The hardware incorporates individual channel configuration settings that define specific input ranges, allowing the concurrent processing of 4-20 mA current loops and 0-10 V voltage signals across separate pins.
Q: What is the mechanical latency introduced by the module sampling architecture?
A: The module executes analog scans at a constant rate of 1 kHz per channel, producing a fresh 16-bit digitized value every 1 ms to minimize data degradation during transient process upsets.
Q: Does the 1500 V RMS isolation safeguard the logic system against ground loops?
A: Yes, the 1500 V RMS galvanic isolation layer breaks electrical paths between the external field wiring loops and the internal processing bus, preventing ground potential differences from corrupting data.
Our production line was down due to a faulty Bently Nevada monitor. We found it in stock here and they shipped it via DHL immediately. Back in operation within 48 hours—truly a lifesaver for our plant.
Finding brand new, original modules is critical for our safety. This team delivers factory-fresh components with full certification. Their commitment to only selling new products makes them our most trusted partner.
We have sourced Honeywell and Schneider parts here for two years. Every shipment arrives well-packaged with original factory seals intact. Clear communication and the best lead times in the industry.