The Yokogawa AAI143-H50/K4A00, also cataloged as the AAI143 Analog Input Module, operates as a dedicated hardware component for 4-20 mA DC signal acquisition with integrated digital communication within CENTUM VP Distributed Control System (DCS) platforms.
| Parameter | Specification |
|---|---|
| Model | AAI143-H50/K4A00 |
| Brand | Yokogawa |
| Origin | Japan |
| Weight | 2.0 kg (Shipping Weight) / Module: 0.30 to 0.45 kg |
| Operating Temp | -20 deg C to +70 deg C |
| Power Consumption | 230 mA (5 V DC), 540 mA (24 V DC) |
| Channels | 16 isolated channels |
| Signal Type | 4-20 mA DC |
| Allowable Input Current | Up to 24 mA |
| Input Resistance | 270 to 350 ohms (Power ON), >= 500 kohms (Power OFF) |
| Accuracy | +/- 16 uA |
| Temperature Drift | +/- 16 uA per 10 deg C |
| Data Update Period | 10 ms |
| Transmitter Power Supply | 19.0 to 25.5 V DC (limit 25 mA) |
| Isolation | 1500 V AC between input and system (1 min) |
The AAI143-H50/K4A00 executes continuous analog-to-digital conversion of 4-20 mA DC signals while concurrently processing HART digital telemetry superimposed on the loop. The "H" suffix denotes hardware native modulation/demodulation components that extract field device diagnostics, calibration parameters, and secondary process variables. Operating alongside the /K4A00 KS Cable Interface, the module routes these secondary digital packets directly to host controller registers without introducing latency to the high-speed 10 ms analog update scan.
Q: What is the primary functional role of the /K4A00 option on this module?
A: The /K4A00 suffix indicates the presence of a dedicated KS Cable Interface Adapter (Model ATK4A-00). This physical adapter allows direct connection between the module and an external AEA4D Terminal Board using standard KS cables.
Q: How does the input impedance characteristic behave under loss-of-power scenarios?
A: During normal operation (Power ON), the channel input resistance remains between 270 and 350 ohms to load the loop properly. If system power is lost (Power OFF), the circuit automatically shifts to a high-impedance state of 500 kohms or greater, electrically decoupling the channel.
Q: Does this module support redundant pairing inside the node nest?
A: Yes. The AAI143-H50/K4A00 supports dual-redundant configurations when mounted in paired slots of an FIO base plate. If a hardware fault occurs, the control system switches input tracking to the adjacent backup unit without signal dropout.