100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

The GE Fanuc IC200UAL006, also cataloged as the IC200UAL006 Micro Programmable Logic Controller, operates as a dedicated hardware component for field signal processing and direct loop control within VersaMax Micro platforms.

Hardware Specifications

Parameter Specification
Model IC200UAL006
Brand GE Fanuc
Origin USA
Weight 2.00 lbs (0.91 kg)
Dimensions Standard VersaMax Micro Chassis Dimensions
Operating Temp 0 to 60 deg C
Power Consumption Operating Voltage: 120 to 240 VAC
Total I/O Points 23 I/O Points
Discrete Channels 13 Inputs / 10 Outputs
Analog Channels 2 Analog Inputs / 1 Analog Output
Communication Ports Port 1: RJ-45 (RS-232), Port 2: DB-15 (RS-485)
User Sensor Power 200 mA at 24 VDC
Max Relay Load 2 A at 240 VAC / 24 VDC (Resistive)

Backplane Bus Communication Velocity & I/O Density Scaling

The IC200UAL006 central processing unit coordinates discrete and analog channel scanning using optimized internal backplane bus communication velocity. Supporting up to 23 built-in I/O channels alongside local sensor power distribution, the unit facilitates direct I/O density scaling via external ribbon cable connection to expansion racks. Embedded serial interfaces support deterministic communications over RS-232 and RS-485 media, while internal non-volatile memory ensures firmware flash compatibility and program retention without relying on external portable memory modules.

Frequently Asked Questions

Q: Does the IC200UAL006 support expansion through portable EEPROM memory modules?

A: No. Portable memory modules are not supported on this specific hardware revision. Program logic and parameter configurations are stored directly in internal non-volatile flash memory.

Q: What are the current and voltage limits for the onboard relay outputs when switching resistive field loads?

A: The integrated relay outputs support a maximum resistive switching load of 2 A per point at either 240 VAC or 24 VDC.

Field Installation Guidelines

  1. Disconnect primary AC line power (120 to 240 VAC) prior to mounting, wiring, or servicing the controller unit.
  2. Secure the IC200UAL006 onto a standard 35 mm DIN rail or surface-mount directly to an earthed panel backplate using M4 screws.
  3. Establish a low-impedance grounding path by connecting the chassis ground terminal to the main panel earth ground point using minimum 14 AWG copper wire.
  4. Route AC power wiring separately from low-voltage DC input/output and serial communication cables to mitigate electromagnetic interference.
  5. Terminate RS-232 communication lines to Port 1 via the RJ-45 connector, and RS-485 serial multidrop network connections to Port 2 via the DB-15 connector.
  6. Ensure total current draw from external field sensors connected to the auxiliary 24 VDC power terminals does not exceed 200 mA.